Kabelarea för 15 Ampere vid 5 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 5 m vid 230V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 2.14V (0.93%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 2.12V (0.92%)
Voltage at Load227.9 VLine Loss: 32.1 W
Max Power & Breaker3.45 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 32.1 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 1.28 V (0.56%) | 228.7 V | 2.12 V (0.92%) | 19.3 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 0.8 V (0.35%) | 229.2 V | 1.32 V (0.58%) | 12.0 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 0.54 V (0.23%) | 229.5 V | 0.88 V (0.38%) | 8.0 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.32 V (0.14%) | 229.7 V | 0.53 V (0.23%) | 4.8 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.2 V (0.09%) | 229.8 V | 0.33 V (0.14%) | 3.0 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.13 V (0.06%) | 229.9 V | 0.21 V (0.09%) | 1.9 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.09 V (0.04%) | 229.9 V | 0.15 V (0.07%) | 1.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.06 V (0.03%) | 229.9 V | 0.11 V (0.05%) | 1.0 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.05 V (0.02%) | 230.0 V | 0.08 V (0.03%) | 0.7 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.03 V (0.01%) | 230.0 V | 0.06 V (0.02%) | 0.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.03 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.02 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.02 V (0.01%) | 230.0 V | 0.03 V (0.01%) | 0.3 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.01 V (0.01%) | 230.0 V | 0.02 V (0.01%) | 0.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.01 V (0.0%) | 230.0 V | 0.02 V (0.01%) | 0.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.01 V (0.0%) | 230.0 V | 0.01 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 15 Ampere vid 5 Meter (230V)
Vilken kabelarea krävs för 15A vid 5 meter (230V)?
För 15 Ampere över 5 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (2.14V / 0.93%).
Hur stor effekt motsvarar 15A vid 230V?
Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.
Related Lengths & Currents (230V)
15A · 10m (230V)15A · 15m (230V)15A · 20m (230V)15A · 25m (230V)15A · 30m (230V)15A · 35m (230V)15A · 40m (230V)15A · 45m (230V)15A · 50m (230V)15A · 60m (230V)15A · 70m (230V)10A · 5m (230V)16A · 5m (230V)20A · 5m (230V)25A · 5m (230V)32A · 5m (230V)40A · 5m (230V)50A · 5m (230V)63A · 5m (230V)80A · 5m (230V)100A · 5m (230V)125A · 5m (230V)160A · 5m (230V)200A · 5m (230V)