⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 15 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 5 m vid 230V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 2.14V (0.93%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 2.12V (0.92%)
Voltage at Load227.9 VLine Loss: 32.1 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.14 V (0.93%)227.9 V3.53 V (1.53%)32.1 W✓ OK (≤3%)
2.5 mm²24 A18 A1.28 V (0.56%)228.7 V2.12 V (0.92%)19.3 W✓ OK (≤3%)
4 mm²32 A25 A0.8 V (0.35%)229.2 V1.32 V (0.58%)12.0 W✓ OK (≤3%)
6 mm²41 A32 A0.54 V (0.23%)229.5 V0.88 V (0.38%)8.0 W✓ OK (≤3%)
10 mm²57 A44 A0.32 V (0.14%)229.7 V0.53 V (0.23%)4.8 W✓ OK (≤3%)
16 mm²76 A59 A0.2 V (0.09%)229.8 V0.33 V (0.14%)3.0 W✓ OK (≤3%)
25 mm²101 A78 A0.13 V (0.06%)229.9 V0.21 V (0.09%)1.9 W✓ OK (≤3%)
35 mm²125 A97 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.4 W✓ OK (≤3%)
50 mm²151 A118 A0.06 V (0.03%)229.9 V0.11 V (0.05%)1.0 W✓ OK (≤3%)
70 mm²192 A150 A0.05 V (0.02%)230.0 V0.08 V (0.03%)0.7 W✓ OK (≤3%)
95 mm²232 A181 A0.03 V (0.01%)230.0 V0.06 V (0.02%)0.5 W✓ OK (≤3%)
120 mm²269 A210 A0.03 V (0.01%)230.0 V0.04 V (0.02%)0.4 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.01%)230.0 V0.04 V (0.02%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.01%)230.0 V0.03 V (0.01%)0.3 W✓ OK (≤3%)
240 mm²415 A324 A0.01 V (0.01%)230.0 V0.02 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.0%)230.0 V0.02 V (0.01%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)230.0 V0.01 V (0.01%)0.1 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 15A vid 5 meter (230V)?

För 15 Ampere över 5 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (2.14V / 0.93%).

Hur stor effekt motsvarar 15A vid 230V?

Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.