⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 15 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 35 m vid 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 6.18V (2.69%)
Voltage at Load224.4 VLine Loss: 84.3 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.98 V (6.51%)215.0 V24.71 V (10.74%)224.7 WDrop High
2.5 mm²24 A18 A8.99 V (3.91%)221.0 V14.83 V (6.45%)134.8 W~ ≤5%
4 mm²32 A25 A5.62 V (2.44%)224.4 V9.27 V (4.03%)84.3 W✓ OK (≤3%)
6 mm²41 A32 A3.75 V (1.63%)226.3 V6.18 V (2.69%)56.2 W✓ OK (≤3%)
10 mm²57 A44 A2.25 V (0.98%)227.8 V3.71 V (1.61%)33.7 W✓ OK (≤3%)
16 mm²76 A59 A1.4 V (0.61%)228.6 V2.32 V (1.01%)21.1 W✓ OK (≤3%)
25 mm²101 A78 A0.9 V (0.39%)229.1 V1.48 V (0.64%)13.5 W✓ OK (≤3%)
35 mm²125 A97 A0.64 V (0.28%)229.4 V1.06 V (0.46%)9.6 W✓ OK (≤3%)
50 mm²151 A118 A0.45 V (0.2%)229.6 V0.74 V (0.32%)6.7 W✓ OK (≤3%)
70 mm²192 A150 A0.32 V (0.14%)229.7 V0.53 V (0.23%)4.8 W✓ OK (≤3%)
95 mm²232 A181 A0.24 V (0.1%)229.8 V0.39 V (0.17%)3.5 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.08%)229.8 V0.31 V (0.13%)2.8 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.07%)229.9 V0.25 V (0.11%)2.2 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.05%)229.9 V0.2 V (0.09%)1.8 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.4 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.12 V (0.05%)1.1 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)229.9 V0.09 V (0.04%)0.8 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 15A vid 35 meter (230V)?

För 15 Ampere över 35 meter vid 230V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (5.62V / 2.44%).

Hur stor effekt motsvarar 15A vid 230V?

Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.