Kabelarea för 15 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 35 m vid 230V.
Copper Cable (≤3% Drop)4 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 6.18V (2.69%)
Voltage at Load224.4 VLine Loss: 84.3 W
Max Power & Breaker3.45 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 224.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 8.99 V (3.91%) | 221.0 V | 14.83 V (6.45%) | 134.8 W | ~ ≤5% |
| 4 mm² | 32 A | 25 A | 5.62 V (2.44%) | 224.4 V | 9.27 V (4.03%) | 84.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.75 V (1.63%) | 226.3 V | 6.18 V (2.69%) | 56.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 2.25 V (0.98%) | 227.8 V | 3.71 V (1.61%) | 33.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.4 V (0.61%) | 228.6 V | 2.32 V (1.01%) | 21.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.9 V (0.39%) | 229.1 V | 1.48 V (0.64%) | 13.5 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.64 V (0.28%) | 229.4 V | 1.06 V (0.46%) | 9.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.45 V (0.2%) | 229.6 V | 0.74 V (0.32%) | 6.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.32 V (0.14%) | 229.7 V | 0.53 V (0.23%) | 4.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.24 V (0.1%) | 229.8 V | 0.39 V (0.17%) | 3.5 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.19 V (0.08%) | 229.8 V | 0.31 V (0.13%) | 2.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.15 V (0.07%) | 229.9 V | 0.25 V (0.11%) | 2.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.12 V (0.05%) | 229.9 V | 0.2 V (0.09%) | 1.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.09 V (0.04%) | 229.9 V | 0.15 V (0.07%) | 1.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.07 V (0.03%) | 229.9 V | 0.12 V (0.05%) | 1.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.06 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 0.8 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 15 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 15A vid 35 meter (230V)?
För 15 Ampere över 35 meter vid 230V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (5.62V / 2.44%).
Hur stor effekt motsvarar 15A vid 230V?
Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.
Related Lengths & Currents (230V)
15A · 5m (230V)15A · 10m (230V)15A · 15m (230V)15A · 20m (230V)15A · 25m (230V)15A · 30m (230V)15A · 40m (230V)15A · 45m (230V)15A · 50m (230V)15A · 60m (230V)15A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)