⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 15 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 45 m vid 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 10.01V (2.5%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 10.32V (2.58%)
Voltage at Load390.0 VLine Loss: 260.0 W
Max Power & Breaker10.39 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A16.68 V (4.17%)383.3 V27.51 V (6.88%)433.4 W~ ≤5%
2.5 mm²24 A18 A10.01 V (2.5%)390.0 V16.51 V (4.13%)260.0 W✓ OK (≤3%)
4 mm²32 A25 A6.25 V (1.56%)393.7 V10.32 V (2.58%)162.5 W✓ OK (≤3%)
6 mm²41 A32 A4.17 V (1.04%)395.8 V6.88 V (1.72%)108.3 W✓ OK (≤3%)
10 mm²57 A44 A2.5 V (0.63%)397.5 V4.13 V (1.03%)65.0 W✓ OK (≤3%)
16 mm²76 A59 A1.56 V (0.39%)398.4 V2.58 V (0.64%)40.6 W✓ OK (≤3%)
25 mm²101 A78 A1.0 V (0.25%)399.0 V1.65 V (0.41%)26.0 W✓ OK (≤3%)
35 mm²125 A97 A0.71 V (0.18%)399.3 V1.18 V (0.29%)18.6 W✓ OK (≤3%)
50 mm²151 A118 A0.5 V (0.13%)399.5 V0.83 V (0.21%)13.0 W✓ OK (≤3%)
70 mm²192 A150 A0.36 V (0.09%)399.6 V0.59 V (0.15%)9.3 W✓ OK (≤3%)
95 mm²232 A181 A0.26 V (0.07%)399.7 V0.43 V (0.11%)6.8 W✓ OK (≤3%)
120 mm²269 A210 A0.21 V (0.05%)399.8 V0.34 V (0.09%)5.4 W✓ OK (≤3%)
150 mm²309 A241 A0.17 V (0.04%)399.8 V0.28 V (0.07%)4.3 W✓ OK (≤3%)
185 mm²353 A275 A0.14 V (0.03%)399.9 V0.22 V (0.06%)3.5 W✓ OK (≤3%)
240 mm²415 A324 A0.1 V (0.03%)399.9 V0.17 V (0.04%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.08 V (0.02%)399.9 V0.14 V (0.03%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)399.9 V0.1 V (0.03%)1.6 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 15A vid 45 meter (400V)?

För 15 Ampere över 45 meter vid 400V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (10.01V / 2.5%).

Hur stor effekt motsvarar 15A vid 400V?

Det motsvarar 10.39 kW med en rekommenderad säkring på 15A.