Kabelarea för 15 Ampere vid 35 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 35 m vid 400V.
Copper Cable (≤3% Drop)2.5 mm²Drop: 7.78V (1.95%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 8.02V (2.01%)
Voltage at Load392.2 VLine Loss: 202.2 W
Max Power & Breaker10.39 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 337.1 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 7.78 V (1.95%) | 392.2 V | 12.84 V (3.21%) | 202.2 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 4.86 V (1.22%) | 395.1 V | 8.02 V (2.01%) | 126.4 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 3.24 V (0.81%) | 396.8 V | 5.35 V (1.34%) | 84.3 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.95 V (0.49%) | 398.1 V | 3.21 V (0.8%) | 50.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.22 V (0.3%) | 398.8 V | 2.01 V (0.5%) | 31.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.78 V (0.19%) | 399.2 V | 1.28 V (0.32%) | 20.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.56 V (0.14%) | 399.4 V | 0.92 V (0.23%) | 14.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.39 V (0.1%) | 399.6 V | 0.64 V (0.16%) | 10.1 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 7.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.2 V (0.05%) | 399.8 V | 0.34 V (0.08%) | 5.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.16 V (0.04%) | 399.8 V | 0.27 V (0.07%) | 4.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.13 V (0.03%) | 399.9 V | 0.21 V (0.05%) | 3.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.11 V (0.03%) | 399.9 V | 0.17 V (0.04%) | 2.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.08 V (0.02%) | 399.9 V | 0.13 V (0.03%) | 2.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.02%) | 399.9 V | 0.11 V (0.03%) | 1.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.05 V (0.01%) | 400.0 V | 0.08 V (0.02%) | 1.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 15 Ampere vid 35 Meter (400V)
Vilken kabelarea krävs för 15A vid 35 meter (400V)?
För 15 Ampere över 35 meter vid 400V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (7.78V / 1.95%).
Hur stor effekt motsvarar 15A vid 400V?
Det motsvarar 10.39 kW med en rekommenderad säkring på 15A.
Related Lengths & Currents (400V)
15A · 5m (400V)15A · 10m (400V)15A · 15m (400V)15A · 20m (400V)15A · 25m (400V)15A · 30m (400V)15A · 40m (400V)15A · 45m (400V)15A · 50m (400V)15A · 60m (400V)15A · 70m (400V)10A · 35m (400V)16A · 35m (400V)20A · 35m (400V)25A · 35m (400V)32A · 35m (400V)40A · 35m (400V)50A · 35m (400V)63A · 35m (400V)80A · 35m (400V)100A · 35m (400V)125A · 35m (400V)160A · 35m (400V)200A · 35m (400V)