Kabelarea för 15 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 35 m vid 400V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 7.78V (1.95%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 8.02V (2.01%)
Voltage at Load392.2 VLine Loss: 202.2 W
Max Power & Breaker10.39 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.97 V (3.24%)387.0 V21.4 V (5.35%)337.1 W~ ≤5%
2.5 mm²24 A18 A7.78 V (1.95%)392.2 V12.84 V (3.21%)202.2 W✓ OK (≤3%)
4 mm²32 A25 A4.86 V (1.22%)395.1 V8.02 V (2.01%)126.4 W✓ OK (≤3%)
6 mm²41 A32 A3.24 V (0.81%)396.8 V5.35 V (1.34%)84.3 W✓ OK (≤3%)
10 mm²57 A44 A1.95 V (0.49%)398.1 V3.21 V (0.8%)50.6 W✓ OK (≤3%)
16 mm²76 A59 A1.22 V (0.3%)398.8 V2.01 V (0.5%)31.6 W✓ OK (≤3%)
25 mm²101 A78 A0.78 V (0.19%)399.2 V1.28 V (0.32%)20.2 W✓ OK (≤3%)
35 mm²125 A97 A0.56 V (0.14%)399.4 V0.92 V (0.23%)14.4 W✓ OK (≤3%)
50 mm²151 A118 A0.39 V (0.1%)399.6 V0.64 V (0.16%)10.1 W✓ OK (≤3%)
70 mm²192 A150 A0.28 V (0.07%)399.7 V0.46 V (0.11%)7.2 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.05%)399.8 V0.34 V (0.08%)5.3 W✓ OK (≤3%)
120 mm²269 A210 A0.16 V (0.04%)399.8 V0.27 V (0.07%)4.2 W✓ OK (≤3%)
150 mm²309 A241 A0.13 V (0.03%)399.9 V0.21 V (0.05%)3.4 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.03%)399.9 V0.17 V (0.04%)2.7 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)399.9 V0.13 V (0.03%)2.1 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)399.9 V0.11 V (0.03%)1.7 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.3 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 15A vid 35 meter (400V)?

För 15 Ampere över 35 meter vid 400V rekommenderas 2.5 mm² kopparkabel för att hålla spänningsfallet under 3% (7.78V / 1.95%).

Hur stor effekt motsvarar 15A vid 400V?

Det motsvarar 10.39 kW med en rekommenderad säkring på 15A.