Kabelarea för 150 Ampere vid 40 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 150 A över 40 m vid 400V.

Copper Cable (≤3% Drop)50 mm²Drop: 4.45V (1.11%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.24V (1.31%)
Voltage at Load395.6 VLine Loss: 1155.6 W
Max Power & Breaker103.92 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A148.26 V (37.07%)251.7 V244.57 V (61.14%)38520.0 WDrop High
2.5 mm²24 A18 A88.96 V (22.24%)311.0 V146.74 V (36.68%)23112.0 WDrop High
4 mm²32 A25 A55.6 V (13.9%)344.4 V91.71 V (22.93%)14445.0 WDrop High
6 mm²41 A32 A37.07 V (9.27%)362.9 V61.14 V (15.29%)9630.0 WDrop High
10 mm²57 A44 A22.24 V (5.56%)377.8 V36.68 V (9.17%)5778.0 WDrop High
16 mm²76 A59 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3611.2 WDrop High
25 mm²101 A78 A8.9 V (2.22%)391.1 V14.67 V (3.67%)2311.2 WDrop High
35 mm²125 A97 A6.35 V (1.59%)393.6 V10.48 V (2.62%)1650.9 WDrop High
50 mm²151 A118 A4.45 V (1.11%)395.6 V7.34 V (1.83%)1155.6 W✓ OK (≤3%)
70 mm²192 A150 A3.18 V (0.79%)396.8 V5.24 V (1.31%)825.4 W✓ OK (≤3%)
95 mm²232 A181 A2.34 V (0.59%)397.7 V3.86 V (0.97%)608.2 W✓ OK (≤3%)
120 mm²269 A210 A1.85 V (0.46%)398.1 V3.06 V (0.76%)481.5 W✓ OK (≤3%)
150 mm²309 A241 A1.48 V (0.37%)398.5 V2.45 V (0.61%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A1.2 V (0.3%)398.8 V1.98 V (0.5%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A0.93 V (0.23%)399.1 V1.53 V (0.38%)240.8 W✓ OK (≤3%)
300 mm²477 A372 A0.74 V (0.19%)399.3 V1.22 V (0.31%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.56 V (0.14%)399.4 V0.92 V (0.23%)144.4 W✓ OK (≤3%)

FAQ — Kabelarea för 150 Ampere vid 40 Meter (400V)

Vilken kabelarea krävs för 150A vid 40 meter (400V)?

För 150 Ampere över 40 meter vid 400V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (4.45V / 1.11%).

Hur stor effekt motsvarar 150A vid 400V?

Det motsvarar 103.92 kW med en rekommenderad säkring på 150A.