Kabelarea för 63 Ampere vid 40 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 40 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 5.84V (1.46%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 6.16V (1.54%)
Voltage at Load394.2 VLine Loss: 637.0 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A62.27 V (15.57%)337.7 V102.72 V (25.68%)6794.9 WDrop High
2.5 mm²24 A18 A37.36 V (9.34%)362.6 V61.63 V (15.41%)4077.0 WDrop High
4 mm²32 A25 A23.35 V (5.84%)376.6 V38.52 V (9.63%)2548.1 WDrop High
6 mm²41 A32 A15.57 V (3.89%)384.4 V25.68 V (6.42%)1698.7 WDrop High
10 mm²57 A44 A9.34 V (2.34%)390.7 V15.41 V (3.85%)1019.2 WDrop High
16 mm²76 A59 A5.84 V (1.46%)394.2 V9.63 V (2.41%)637.0 W✓ OK (≤3%)
25 mm²101 A78 A3.74 V (0.93%)396.3 V6.16 V (1.54%)407.7 W✓ OK (≤3%)
35 mm²125 A97 A2.67 V (0.67%)397.3 V4.4 V (1.1%)291.2 W✓ OK (≤3%)
50 mm²151 A118 A1.87 V (0.47%)398.1 V3.08 V (0.77%)203.8 W✓ OK (≤3%)
70 mm²192 A150 A1.33 V (0.33%)398.7 V2.2 V (0.55%)145.6 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.25%)399.0 V1.62 V (0.41%)107.3 W✓ OK (≤3%)
120 mm²269 A210 A0.78 V (0.19%)399.2 V1.28 V (0.32%)84.9 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.16%)399.4 V1.03 V (0.26%)67.9 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.13%)399.5 V0.83 V (0.21%)55.1 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.1%)399.6 V0.64 V (0.16%)42.5 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.08%)399.7 V0.51 V (0.13%)34.0 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.39 V (0.1%)25.5 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 40 Meter (400V)

Vilken kabelarea krävs för 63A vid 40 meter (400V)?

För 63 Ampere över 40 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (5.84V / 1.46%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.