Kabelarea för 150 Ampere vid 5 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 150 A över 5 m vid 400V.
Copper Cable (≤3% Drop)50 mm²Drop: 0.56V (0.14%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 0.66V (0.16%)
Voltage at Load399.4 VLine Loss: 144.4 W
Max Power & Breaker103.92 kW150A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 4815.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 11.12 V (2.78%) | 388.9 V | 18.34 V (4.59%) | 2889.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 6.95 V (1.74%) | 393.1 V | 11.46 V (2.87%) | 1805.6 W | Drop High |
| 6 mm² | 41 A | 32 A | 4.63 V (1.16%) | 395.4 V | 7.64 V (1.91%) | 1203.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 2.78 V (0.69%) | 397.2 V | 4.59 V (1.15%) | 722.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 1.74 V (0.43%) | 398.3 V | 2.87 V (0.72%) | 451.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 1.11 V (0.28%) | 398.9 V | 1.83 V (0.46%) | 288.9 W | Drop High |
| 35 mm² | 125 A | 97 A | 0.79 V (0.2%) | 399.2 V | 1.31 V (0.33%) | 206.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 0.56 V (0.14%) | 399.4 V | 0.92 V (0.23%) | 144.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.4 V (0.1%) | 399.6 V | 0.66 V (0.16%) | 103.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.29 V (0.07%) | 399.7 V | 0.48 V (0.12%) | 76.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.23 V (0.06%) | 399.8 V | 0.38 V (0.1%) | 60.2 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.19 V (0.05%) | 399.8 V | 0.31 V (0.08%) | 48.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.15 V (0.04%) | 399.8 V | 0.25 V (0.06%) | 39.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.12 V (0.03%) | 399.9 V | 0.19 V (0.05%) | 30.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 24.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.07 V (0.02%) | 399.9 V | 0.11 V (0.03%) | 18.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 150 Ampere vid 5 Meter (400V)
Vilken kabelarea krävs för 150A vid 5 meter (400V)?
För 150 Ampere över 5 meter vid 400V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (0.56V / 0.14%).
Hur stor effekt motsvarar 150A vid 400V?
Det motsvarar 103.92 kW med en rekommenderad säkring på 150A.
Related Lengths & Currents (400V)
150A · 10m (400V)150A · 15m (400V)150A · 20m (400V)150A · 25m (400V)150A · 30m (400V)150A · 35m (400V)150A · 40m (400V)150A · 45m (400V)150A · 50m (400V)150A · 60m (400V)150A · 70m (400V)10A · 5m (400V)16A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)200A · 5m (400V)