Kabelarea för 200 Ampere vid 5 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 5 m vid 400V.
Copper Cable (≤3% Drop)95 mm²Drop: 0.39V (0.1%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.51V (0.13%)
Voltage at Load399.6 VLine Loss: 135.2 W
Max Power & Breaker138.56 kW200A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 24.71 V (6.18%) | 375.3 V | 40.76 V (10.19%) | 8560.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 14.83 V (3.71%) | 385.2 V | 24.46 V (6.11%) | 5136.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 3210.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 6.18 V (1.54%) | 393.8 V | 10.19 V (2.55%) | 2140.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 3.71 V (0.93%) | 396.3 V | 6.11 V (1.53%) | 1284.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 802.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 1.48 V (0.37%) | 398.5 V | 2.45 V (0.61%) | 513.6 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.06 V (0.26%) | 398.9 V | 1.75 V (0.44%) | 366.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 0.74 V (0.19%) | 399.3 V | 1.22 V (0.31%) | 256.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 0.53 V (0.13%) | 399.5 V | 0.87 V (0.22%) | 183.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 0.39 V (0.1%) | 399.6 V | 0.64 V (0.16%) | 135.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.31 V (0.08%) | 399.7 V | 0.51 V (0.13%) | 107.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.25 V (0.06%) | 399.8 V | 0.41 V (0.1%) | 85.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.2 V (0.05%) | 399.8 V | 0.33 V (0.08%) | 69.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.15 V (0.04%) | 399.8 V | 0.25 V (0.06%) | 53.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.12 V (0.03%) | 399.9 V | 0.2 V (0.05%) | 42.8 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 32.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 200 Ampere vid 5 Meter (400V)
Vilken kabelarea krävs för 200A vid 5 meter (400V)?
För 200 Ampere över 5 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (0.39V / 0.1%).
Hur stor effekt motsvarar 200A vid 400V?
Det motsvarar 138.56 kW med en rekommenderad säkring på 200A.
Related Lengths & Currents (400V)
200A · 10m (400V)200A · 15m (400V)200A · 20m (400V)200A · 25m (400V)200A · 30m (400V)200A · 35m (400V)200A · 40m (400V)200A · 45m (400V)200A · 50m (400V)200A · 60m (400V)200A · 70m (400V)10A · 5m (400V)16A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)