Kabelarea för 150 Ampere vid 60 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 150 A över 60 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 5.5V (2.39%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 6.69V (2.91%)
Voltage at Load224.5 VLine Loss: 825.4 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A256.8 V (111.65%)0.0 V423.6 V (184.17%)38520.0 WDrop High
2.5 mm²24 A18 A154.08 V (66.99%)75.9 V254.16 V (110.5%)23112.0 WDrop High
4 mm²32 A25 A96.3 V (41.87%)133.7 V158.85 V (69.07%)14445.0 WDrop High
6 mm²41 A32 A64.2 V (27.91%)165.8 V105.9 V (46.04%)9630.0 WDrop High
10 mm²57 A44 A38.52 V (16.75%)191.5 V63.54 V (27.63%)5778.0 WDrop High
16 mm²76 A59 A24.07 V (10.47%)205.9 V39.71 V (17.27%)3611.2 WDrop High
25 mm²101 A78 A15.41 V (6.7%)214.6 V25.42 V (11.05%)2311.2 WDrop High
35 mm²125 A97 A11.01 V (4.79%)219.0 V18.15 V (7.89%)1650.9 WDrop High
50 mm²151 A118 A7.7 V (3.35%)222.3 V12.71 V (5.53%)1155.6 W~ ≤5%
70 mm²192 A150 A5.5 V (2.39%)224.5 V9.08 V (3.95%)825.4 W✓ OK (≤3%)
95 mm²232 A181 A4.05 V (1.76%)225.9 V6.69 V (2.91%)608.2 W✓ OK (≤3%)
120 mm²269 A210 A3.21 V (1.4%)226.8 V5.29 V (2.3%)481.5 W✓ OK (≤3%)
150 mm²309 A241 A2.57 V (1.12%)227.4 V4.24 V (1.84%)385.2 W✓ OK (≤3%)
185 mm²353 A275 A2.08 V (0.91%)227.9 V3.43 V (1.49%)312.3 W✓ OK (≤3%)
240 mm²415 A324 A1.6 V (0.7%)228.4 V2.65 V (1.15%)240.8 W✓ OK (≤3%)
300 mm²477 A372 A1.28 V (0.56%)228.7 V2.12 V (0.92%)192.6 W✓ OK (≤3%)
400 mm²570 A445 A0.96 V (0.42%)229.0 V1.59 V (0.69%)144.5 W✓ OK (≤3%)

FAQ — Kabelarea för 150 Ampere vid 60 Meter (230V)

Vilken kabelarea krävs för 150A vid 60 meter (230V)?

För 150 Ampere över 60 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (5.5V / 2.39%).

Hur stor effekt motsvarar 150A vid 230V?

Det motsvarar 34.5 kW med en rekommenderad säkring på 150A.