Kabelarea för 80 Ampere vid 60 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 60 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.87V (2.55%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.78V (2.95%)
Voltage at Load224.1 VLine Loss: 469.6 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A136.96 V (59.55%)93.0 V225.92 V (98.23%)10956.8 WDrop High
2.5 mm²24 A18 A82.18 V (35.73%)147.8 V135.55 V (58.94%)6574.1 WDrop High
4 mm²32 A25 A51.36 V (22.33%)178.6 V84.72 V (36.83%)4108.8 WDrop High
6 mm²41 A32 A34.24 V (14.89%)195.8 V56.48 V (24.56%)2739.2 WDrop High
10 mm²57 A44 A20.54 V (8.93%)209.5 V33.89 V (14.73%)1643.5 WDrop High
16 mm²76 A59 A12.84 V (5.58%)217.2 V21.18 V (9.21%)1027.2 WDrop High
25 mm²101 A78 A8.22 V (3.57%)221.8 V13.56 V (5.89%)657.4 W~ ≤5%
35 mm²125 A97 A5.87 V (2.55%)224.1 V9.68 V (4.21%)469.6 W✓ OK (≤3%)
50 mm²151 A118 A4.11 V (1.79%)225.9 V6.78 V (2.95%)328.7 W✓ OK (≤3%)
70 mm²192 A150 A2.93 V (1.28%)227.1 V4.84 V (2.1%)234.8 W✓ OK (≤3%)
95 mm²232 A181 A2.16 V (0.94%)227.8 V3.57 V (1.55%)173.0 W✓ OK (≤3%)
120 mm²269 A210 A1.71 V (0.74%)228.3 V2.82 V (1.23%)137.0 W✓ OK (≤3%)
150 mm²309 A241 A1.37 V (0.6%)228.6 V2.26 V (0.98%)109.6 W✓ OK (≤3%)
185 mm²353 A275 A1.11 V (0.48%)228.9 V1.83 V (0.8%)88.8 W✓ OK (≤3%)
240 mm²415 A324 A0.86 V (0.37%)229.1 V1.41 V (0.61%)68.5 W✓ OK (≤3%)
300 mm²477 A372 A0.68 V (0.3%)229.3 V1.13 V (0.49%)54.8 W✓ OK (≤3%)
400 mm²570 A445 A0.51 V (0.22%)229.5 V0.85 V (0.37%)41.1 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 60 Meter (230V)

Vilken kabelarea krävs för 80A vid 60 meter (230V)?

För 80 Ampere över 60 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (5.87V / 2.55%).

Hur stor effekt motsvarar 80A vid 230V?

Det motsvarar 18.4 kW med en rekommenderad säkring på 80A.