Kabelarea för 63 Ampere vid 60 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 60 m vid 230V.
Copper Cable (≤3% Drop)25 mm²Drop: 6.47V (2.81%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 5.34V (2.32%)
Voltage at Load223.5 VLine Loss: 407.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 60m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 107.86 V (46.89%) | 122.1 V | 177.91 V (77.35%) | 6794.9 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 64.71 V (28.14%) | 165.3 V | 106.75 V (46.41%) | 4077.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 40.45 V (17.59%) | 189.6 V | 66.72 V (29.01%) | 2548.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 26.96 V (11.72%) | 203.0 V | 44.48 V (19.34%) | 1698.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 16.18 V (7.03%) | 213.8 V | 26.69 V (11.6%) | 1019.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 10.11 V (4.4%) | 219.9 V | 16.68 V (7.25%) | 637.0 W | ~ ≤5% |
| 25 mm² | 101 A | 78 A | 6.47 V (2.81%) | 223.5 V | 10.67 V (4.64%) | 407.7 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 4.62 V (2.01%) | 225.4 V | 7.62 V (3.32%) | 291.2 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.24 V (1.41%) | 226.8 V | 5.34 V (2.32%) | 203.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.31 V (1.0%) | 227.7 V | 3.81 V (1.66%) | 145.6 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.7 V (0.74%) | 228.3 V | 2.81 V (1.22%) | 107.3 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.35 V (0.59%) | 228.7 V | 2.22 V (0.97%) | 84.9 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.08 V (0.47%) | 228.9 V | 1.78 V (0.77%) | 67.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.87 V (0.38%) | 229.1 V | 1.44 V (0.63%) | 55.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.67 V (0.29%) | 229.3 V | 1.11 V (0.48%) | 42.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.54 V (0.23%) | 229.5 V | 0.89 V (0.39%) | 34.0 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.4 V (0.18%) | 229.6 V | 0.67 V (0.29%) | 25.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 63 Ampere vid 60 Meter (230V)
Vilken kabelarea krävs för 63A vid 60 meter (230V)?
För 63 Ampere över 60 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (6.47V / 2.81%).
Hur stor effekt motsvarar 63A vid 230V?
Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.
Related Lengths & Currents (230V)
63A · 5m (230V)63A · 10m (230V)63A · 15m (230V)63A · 20m (230V)63A · 25m (230V)63A · 30m (230V)63A · 35m (230V)63A · 40m (230V)63A · 45m (230V)63A · 50m (230V)63A · 70m (230V)10A · 60m (230V)16A · 60m (230V)20A · 60m (230V)25A · 60m (230V)32A · 60m (230V)40A · 60m (230V)50A · 60m (230V)80A · 60m (230V)100A · 60m (230V)125A · 60m (230V)160A · 60m (230V)200A · 60m (230V)