Kabelarea för 160 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 160 A över 5 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 0.49V (0.21%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 0.59V (0.26%)
Voltage at Load229.5 VLine Loss: 78.3 W
Max Power & Breaker36.8 kW160A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A22.83 V (9.92%)207.2 V37.65 V (16.37%)3652.3 WDrop High
2.5 mm²24 A18 A13.7 V (5.95%)216.3 V22.59 V (9.82%)2191.4 WDrop High
4 mm²32 A25 A8.56 V (3.72%)221.4 V14.12 V (6.14%)1369.6 WDrop High
6 mm²41 A32 A5.71 V (2.48%)224.3 V9.41 V (4.09%)913.1 WDrop High
10 mm²57 A44 A3.42 V (1.49%)226.6 V5.65 V (2.46%)547.8 WDrop High
16 mm²76 A59 A2.14 V (0.93%)227.9 V3.53 V (1.53%)342.4 WDrop High
25 mm²101 A78 A1.37 V (0.6%)228.6 V2.26 V (0.98%)219.1 WDrop High
35 mm²125 A97 A0.98 V (0.43%)229.0 V1.61 V (0.7%)156.5 WDrop High
50 mm²151 A118 A0.68 V (0.3%)229.3 V1.13 V (0.49%)109.6 WDrop High
70 mm²192 A150 A0.49 V (0.21%)229.5 V0.81 V (0.35%)78.3 W✓ OK (≤3%)
95 mm²232 A181 A0.36 V (0.16%)229.6 V0.59 V (0.26%)57.7 W✓ OK (≤3%)
120 mm²269 A210 A0.29 V (0.12%)229.7 V0.47 V (0.2%)45.7 W✓ OK (≤3%)
150 mm²309 A241 A0.23 V (0.1%)229.8 V0.38 V (0.16%)36.5 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.08%)229.8 V0.31 V (0.13%)29.6 W✓ OK (≤3%)
240 mm²415 A324 A0.14 V (0.06%)229.9 V0.24 V (0.1%)22.8 W✓ OK (≤3%)
300 mm²477 A372 A0.11 V (0.05%)229.9 V0.19 V (0.08%)18.3 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.04%)229.9 V0.14 V (0.06%)13.7 W✓ OK (≤3%)

FAQ — Kabelarea för 160 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 160A vid 5 meter (230V)?

För 160 Ampere över 5 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (0.49V / 0.21%).

Hur stor effekt motsvarar 160A vid 230V?

Det motsvarar 36.8 kW med en rekommenderad säkring på 160A.