⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 200 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 60 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 4.68V (1.17%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 6.11V (1.53%)
Voltage at Load395.3 VLine Loss: 1621.9 W
Max Power & Breaker138.56 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A296.53 V (74.13%)103.5 V489.13 V (122.28%)102720.0 WDrop High
2.5 mm²24 A18 A177.92 V (44.48%)222.1 V293.48 V (73.37%)61632.0 WDrop High
4 mm²32 A25 A111.2 V (27.8%)288.8 V183.42 V (45.86%)38520.0 WDrop High
6 mm²41 A32 A74.13 V (18.53%)325.9 V122.28 V (30.57%)25680.0 WDrop High
10 mm²57 A44 A44.48 V (11.12%)355.5 V73.37 V (18.34%)15408.0 WDrop High
16 mm²76 A59 A27.8 V (6.95%)372.2 V45.86 V (11.46%)9630.0 WDrop High
25 mm²101 A78 A17.79 V (4.45%)382.2 V29.35 V (7.34%)6163.2 WDrop High
35 mm²125 A97 A12.71 V (3.18%)387.3 V20.96 V (5.24%)4402.3 WDrop High
50 mm²151 A118 A8.9 V (2.22%)391.1 V14.67 V (3.67%)3081.6 WDrop High
70 mm²192 A150 A6.35 V (1.59%)393.6 V10.48 V (2.62%)2201.1 WDrop High
95 mm²232 A181 A4.68 V (1.17%)395.3 V7.72 V (1.93%)1621.9 W✓ OK (≤3%)
120 mm²269 A210 A3.71 V (0.93%)396.3 V6.11 V (1.53%)1284.0 W✓ OK (≤3%)
150 mm²309 A241 A2.97 V (0.74%)397.0 V4.89 V (1.22%)1027.2 W✓ OK (≤3%)
185 mm²353 A275 A2.4 V (0.6%)397.6 V3.97 V (0.99%)832.9 W✓ OK (≤3%)
240 mm²415 A324 A1.85 V (0.46%)398.1 V3.06 V (0.76%)642.0 W✓ OK (≤3%)
300 mm²477 A372 A1.48 V (0.37%)398.5 V2.45 V (0.61%)513.6 W✓ OK (≤3%)
400 mm²570 A445 A1.11 V (0.28%)398.9 V1.83 V (0.46%)385.2 W✓ OK (≤3%)

FAQ — Kabelarea för 200 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 200A vid 60 meter (400V)?

För 200 Ampere över 60 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (4.68V / 1.17%).

Hur stor effekt motsvarar 200A vid 400V?

Det motsvarar 138.56 kW med en rekommenderad säkring på 200A.