⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 200 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 200 A över 5 m vid 230V.

Copper Cable (≤3% Drop)95 mm²Drop: 0.45V (0.2%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 0.59V (0.26%)
Voltage at Load229.5 VLine Loss: 90.1 W
Max Power & Breaker46.0 kW200A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 200A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A28.53 V (12.41%)201.5 V47.07 V (20.46%)5706.7 WDrop High
2.5 mm²24 A18 A17.12 V (7.44%)212.9 V28.24 V (12.28%)3424.0 WDrop High
4 mm²32 A25 A10.7 V (4.65%)219.3 V17.65 V (7.67%)2140.0 WDrop High
6 mm²41 A32 A7.13 V (3.1%)222.9 V11.77 V (5.12%)1426.7 WDrop High
10 mm²57 A44 A4.28 V (1.86%)225.7 V7.06 V (3.07%)856.0 WDrop High
16 mm²76 A59 A2.67 V (1.16%)227.3 V4.41 V (1.92%)535.0 WDrop High
25 mm²101 A78 A1.71 V (0.74%)228.3 V2.82 V (1.23%)342.4 WDrop High
35 mm²125 A97 A1.22 V (0.53%)228.8 V2.02 V (0.88%)244.6 WDrop High
50 mm²151 A118 A0.86 V (0.37%)229.1 V1.41 V (0.61%)171.2 WDrop High
70 mm²192 A150 A0.61 V (0.27%)229.4 V1.01 V (0.44%)122.3 WDrop High
95 mm²232 A181 A0.45 V (0.2%)229.5 V0.74 V (0.32%)90.1 W✓ OK (≤3%)
120 mm²269 A210 A0.36 V (0.16%)229.6 V0.59 V (0.26%)71.3 W✓ OK (≤3%)
150 mm²309 A241 A0.29 V (0.12%)229.7 V0.47 V (0.2%)57.1 W✓ OK (≤3%)
185 mm²353 A275 A0.23 V (0.1%)229.8 V0.38 V (0.17%)46.3 W✓ OK (≤3%)
240 mm²415 A324 A0.18 V (0.08%)229.8 V0.29 V (0.13%)35.7 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.06%)229.9 V0.24 V (0.1%)28.5 W✓ OK (≤3%)
400 mm²570 A445 A0.11 V (0.05%)229.9 V0.18 V (0.08%)21.4 W✓ OK (≤3%)

FAQ — Kabelarea för 200 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 200A vid 5 meter (230V)?

För 200 Ampere över 5 meter vid 230V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (0.45V / 0.2%).

Hur stor effekt motsvarar 200A vid 230V?

Det motsvarar 46.0 kW med en rekommenderad säkring på 200A.