Kabelarea för 275 Ampere vid 40 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 40 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 2.72V (0.68%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 3.64V (0.91%)
Voltage at Load397.3 VLine Loss: 1294.7 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A271.82 V (67.95%)128.2 V448.37 V (112.09%)129470.0 WDrop High
2.5 mm²24 A18 A163.09 V (40.77%)236.9 V269.02 V (67.26%)77682.0 WDrop High
4 mm²32 A25 A101.93 V (25.48%)298.1 V168.14 V (42.03%)48551.2 WDrop High
6 mm²41 A32 A67.95 V (16.99%)332.0 V112.09 V (28.02%)32367.5 WDrop High
10 mm²57 A44 A40.77 V (10.19%)359.2 V67.26 V (16.81%)19420.5 WDrop High
16 mm²76 A59 A25.48 V (6.37%)374.5 V42.03 V (10.51%)12137.8 WDrop High
25 mm²101 A78 A16.31 V (4.08%)383.7 V26.9 V (6.73%)7768.2 WDrop High
35 mm²125 A97 A11.65 V (2.91%)388.4 V19.22 V (4.8%)5548.7 WDrop High
50 mm²151 A118 A8.15 V (2.04%)391.8 V13.45 V (3.36%)3884.1 WDrop High
70 mm²192 A150 A5.82 V (1.46%)394.2 V9.61 V (2.4%)2774.4 WDrop High
95 mm²232 A181 A4.29 V (1.07%)395.7 V7.08 V (1.77%)2044.3 WDrop High
120 mm²269 A210 A3.4 V (0.85%)396.6 V5.6 V (1.4%)1618.4 WDrop High
150 mm²309 A241 A2.72 V (0.68%)397.3 V4.48 V (1.12%)1294.7 W✓ OK (≤3%)
185 mm²353 A275 A2.2 V (0.55%)397.8 V3.64 V (0.91%)1049.8 W✓ OK (≤3%)
240 mm²415 A324 A1.7 V (0.42%)398.3 V2.8 V (0.7%)809.2 W✓ OK (≤3%)
300 mm²477 A372 A1.36 V (0.34%)398.6 V2.24 V (0.56%)647.3 W✓ OK (≤3%)
400 mm²570 A445 A1.02 V (0.25%)399.0 V1.68 V (0.42%)485.5 W✓ OK (≤3%)