⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 275 Ampere vid 5 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 5 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 0.34V (0.08%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.45V (0.11%)
Voltage at Load399.7 VLine Loss: 161.8 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A33.98 V (8.49%)366.0 V56.05 V (14.01%)16183.8 WDrop High
2.5 mm²24 A18 A20.39 V (5.1%)379.6 V33.63 V (8.41%)9710.2 WDrop High
4 mm²32 A25 A12.74 V (3.19%)387.3 V21.02 V (5.25%)6068.9 WDrop High
6 mm²41 A32 A8.49 V (2.12%)391.5 V14.01 V (3.5%)4045.9 WDrop High
10 mm²57 A44 A5.1 V (1.27%)394.9 V8.41 V (2.1%)2427.6 WDrop High
16 mm²76 A59 A3.19 V (0.8%)396.8 V5.25 V (1.31%)1517.2 WDrop High
25 mm²101 A78 A2.04 V (0.51%)398.0 V3.36 V (0.84%)971.0 WDrop High
35 mm²125 A97 A1.46 V (0.36%)398.5 V2.4 V (0.6%)693.6 WDrop High
50 mm²151 A118 A1.02 V (0.25%)399.0 V1.68 V (0.42%)485.5 WDrop High
70 mm²192 A150 A0.73 V (0.18%)399.3 V1.2 V (0.3%)346.8 WDrop High
95 mm²232 A181 A0.54 V (0.13%)399.5 V0.88 V (0.22%)255.5 WDrop High
120 mm²269 A210 A0.42 V (0.11%)399.6 V0.7 V (0.18%)202.3 WDrop High
150 mm²309 A241 A0.34 V (0.08%)399.7 V0.56 V (0.14%)161.8 W✓ OK (≤3%)
185 mm²353 A275 A0.28 V (0.07%)399.7 V0.45 V (0.11%)131.2 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.05%)399.8 V0.35 V (0.09%)101.1 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)399.8 V0.28 V (0.07%)80.9 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.21 V (0.05%)60.7 W✓ OK (≤3%)

FAQ — Kabelarea för 275 Ampere vid 5 Meter (400V)

Vilken kabelarea krävs för 275A vid 5 meter (400V)?

För 275 Ampere över 5 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (0.34V / 0.08%).

Hur stor effekt motsvarar 275A vid 400V?

Det motsvarar 190.53 kW med en rekommenderad säkring på 300A.