Kabelarea för 275 Ampere vid 5 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 5 m vid 400V.
Copper Cable (≤3% Drop)150 mm²Drop: 0.34V (0.08%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 0.45V (0.11%)
Voltage at Load399.7 VLine Loss: 161.8 W
Max Power & Breaker190.53 kW300A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 5m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 33.98 V (8.49%) | 366.0 V | 56.05 V (14.01%) | 16183.8 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 20.39 V (5.1%) | 379.6 V | 33.63 V (8.41%) | 9710.2 W | Drop High |
| 4 mm² | 32 A | 25 A | 12.74 V (3.19%) | 387.3 V | 21.02 V (5.25%) | 6068.9 W | Drop High |
| 6 mm² | 41 A | 32 A | 8.49 V (2.12%) | 391.5 V | 14.01 V (3.5%) | 4045.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 5.1 V (1.27%) | 394.9 V | 8.41 V (2.1%) | 2427.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 3.19 V (0.8%) | 396.8 V | 5.25 V (1.31%) | 1517.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 2.04 V (0.51%) | 398.0 V | 3.36 V (0.84%) | 971.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 1.46 V (0.36%) | 398.5 V | 2.4 V (0.6%) | 693.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 1.02 V (0.25%) | 399.0 V | 1.68 V (0.42%) | 485.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 0.73 V (0.18%) | 399.3 V | 1.2 V (0.3%) | 346.8 W | Drop High |
| 95 mm² | 232 A | 181 A | 0.54 V (0.13%) | 399.5 V | 0.88 V (0.22%) | 255.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 0.42 V (0.11%) | 399.6 V | 0.7 V (0.18%) | 202.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 0.34 V (0.08%) | 399.7 V | 0.56 V (0.14%) | 161.8 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.28 V (0.07%) | 399.7 V | 0.45 V (0.11%) | 131.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.21 V (0.05%) | 399.8 V | 0.35 V (0.09%) | 101.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.17 V (0.04%) | 399.8 V | 0.28 V (0.07%) | 80.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.13 V (0.03%) | 399.9 V | 0.21 V (0.05%) | 60.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 275 Ampere vid 5 Meter (400V)
Vilken kabelarea krävs för 275A vid 5 meter (400V)?
För 275 Ampere över 5 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (0.34V / 0.08%).
Hur stor effekt motsvarar 275A vid 400V?
Det motsvarar 190.53 kW med en rekommenderad säkring på 300A.
Related Lengths & Currents (400V)
275A · 10m (400V)275A · 15m (400V)275A · 20m (400V)275A · 25m (400V)275A · 30m (400V)275A · 35m (400V)275A · 40m (400V)275A · 45m (400V)275A · 50m (400V)275A · 60m (400V)275A · 70m (400V)10A · 5m (400V)16A · 5m (400V)20A · 5m (400V)25A · 5m (400V)32A · 5m (400V)40A · 5m (400V)50A · 5m (400V)63A · 5m (400V)80A · 5m (400V)100A · 5m (400V)125A · 5m (400V)160A · 5m (400V)200A · 5m (400V)