Kabelarea för 30 Ampere vid 5 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 30 A över 5 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 1.39V (0.35%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 1.53V (0.38%)
Voltage at Load398.6 VLine Loss: 72.2 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.71 V (0.93%)396.3 V6.11 V (1.53%)192.6 WDrop High
2.5 mm²24 A18 A2.22 V (0.56%)397.8 V3.67 V (0.92%)115.6 WDrop High
4 mm²32 A25 A1.39 V (0.35%)398.6 V2.29 V (0.57%)72.2 W✓ OK (≤3%)
6 mm²41 A32 A0.93 V (0.23%)399.1 V1.53 V (0.38%)48.1 W✓ OK (≤3%)
10 mm²57 A44 A0.56 V (0.14%)399.4 V0.92 V (0.23%)28.9 W✓ OK (≤3%)
16 mm²76 A59 A0.35 V (0.09%)399.7 V0.57 V (0.14%)18.1 W✓ OK (≤3%)
25 mm²101 A78 A0.22 V (0.06%)399.8 V0.37 V (0.09%)11.6 W✓ OK (≤3%)
35 mm²125 A97 A0.16 V (0.04%)399.8 V0.26 V (0.07%)8.3 W✓ OK (≤3%)
50 mm²151 A118 A0.11 V (0.03%)399.9 V0.18 V (0.05%)5.8 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.02%)399.9 V0.13 V (0.03%)4.1 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.01%)399.9 V0.1 V (0.02%)3.0 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.4 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.01%)400.0 V0.06 V (0.02%)1.9 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.6 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)400.0 V0.04 V (0.01%)1.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)1.0 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.7 W✓ OK (≤3%)

FAQ — Kabelarea för 30 Ampere vid 5 Meter (400V)

Vilken kabelarea krävs för 30A vid 5 meter (400V)?

För 30 Ampere över 5 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (1.39V / 0.35%).

Hur stor effekt motsvarar 30A vid 400V?

Det motsvarar 20.78 kW med en rekommenderad säkring på 30A.