Kabelarea för 30 Ampere vid 70 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 30 A över 70 m vid 400V.
Copper Cable (≤3% Drop)10 mm²Drop: 7.78V (1.95%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 8.02V (2.01%)
Voltage at Load392.2 VLine Loss: 404.5 W
Max Power & Breaker20.78 kW30A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 51.89 V (12.97%) | 348.1 V | 85.6 V (21.4%) | 2696.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 31.14 V (7.78%) | 368.9 V | 51.36 V (12.84%) | 1617.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 19.46 V (4.86%) | 380.5 V | 32.1 V (8.02%) | 1011.1 W | ~ ≤5% |
| 6 mm² | 41 A | 32 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 674.1 W | ~ ≤5% |
| 10 mm² | 57 A | 44 A | 7.78 V (1.95%) | 392.2 V | 12.84 V (3.21%) | 404.5 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 4.86 V (1.22%) | 395.1 V | 8.02 V (2.01%) | 252.8 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.11 V (0.78%) | 396.9 V | 5.14 V (1.28%) | 161.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.22 V (0.56%) | 397.8 V | 3.67 V (0.92%) | 115.6 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.56 V (0.39%) | 398.4 V | 2.57 V (0.64%) | 80.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.11 V (0.28%) | 398.9 V | 1.83 V (0.46%) | 57.8 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.82 V (0.2%) | 399.2 V | 1.35 V (0.34%) | 42.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.65 V (0.16%) | 399.4 V | 1.07 V (0.27%) | 33.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 27.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.42 V (0.11%) | 399.6 V | 0.69 V (0.17%) | 21.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.32 V (0.08%) | 399.7 V | 0.53 V (0.13%) | 16.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.26 V (0.06%) | 399.7 V | 0.43 V (0.11%) | 13.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.19 V (0.05%) | 399.8 V | 0.32 V (0.08%) | 10.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 30 Ampere vid 70 Meter (400V)
Vilken kabelarea krävs för 30A vid 70 meter (400V)?
För 30 Ampere över 70 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (7.78V / 1.95%).
Hur stor effekt motsvarar 30A vid 400V?
Det motsvarar 20.78 kW med en rekommenderad säkring på 30A.
Related Lengths & Currents (400V)
30A · 5m (400V)30A · 10m (400V)30A · 15m (400V)30A · 20m (400V)30A · 25m (400V)30A · 30m (400V)30A · 35m (400V)30A · 40m (400V)30A · 45m (400V)30A · 50m (400V)30A · 60m (400V)10A · 70m (400V)16A · 70m (400V)20A · 70m (400V)25A · 70m (400V)32A · 70m (400V)40A · 70m (400V)50A · 70m (400V)63A · 70m (400V)80A · 70m (400V)100A · 70m (400V)125A · 70m (400V)160A · 70m (400V)200A · 70m (400V)