Kabelarea för 300 Ampere vid 175 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 300 A över 175 m vid 230V.
Copper Cable (≤3% Drop)400 mm²Drop: 5.62V (2.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.27V (4.03%)
Voltage at Load224.4 VLine Loss: 1685.2 W
Max Power & Breaker69.0 kW300A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1498.0 V (651.3%) | 0.0 V | 2471.0 V (1074.35%) | 449400.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 898.8 V (390.78%) | 0.0 V | 1482.6 V (644.61%) | 269640.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 561.75 V (244.24%) | 0.0 V | 926.62 V (402.88%) | 168525.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 374.5 V (162.83%) | 0.0 V | 617.75 V (268.59%) | 112350.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 224.7 V (97.7%) | 5.3 V | 370.65 V (161.15%) | 67410.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 140.44 V (61.06%) | 89.6 V | 231.66 V (100.72%) | 42131.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 89.88 V (39.08%) | 140.1 V | 148.26 V (64.46%) | 26964.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 64.2 V (27.91%) | 165.8 V | 105.9 V (46.04%) | 19260.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 44.94 V (19.54%) | 185.1 V | 74.13 V (32.23%) | 13482.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 32.1 V (13.96%) | 197.9 V | 52.95 V (23.02%) | 9630.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 23.65 V (10.28%) | 206.3 V | 39.02 V (16.96%) | 7095.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 18.72 V (8.14%) | 211.3 V | 30.89 V (13.43%) | 5617.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 4494.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 12.15 V (5.28%) | 217.9 V | 20.04 V (8.71%) | 3643.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 9.36 V (4.07%) | 220.6 V | 15.44 V (6.71%) | 2808.8 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 7.49 V (3.26%) | 222.5 V | 12.35 V (5.37%) | 2247.0 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 5.62 V (2.44%) | 224.4 V | 9.27 V (4.03%) | 1685.2 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 300 Ampere vid 175 Meter (230V)
Vilken kabelarea krävs för 300A vid 175 meter (230V)?
För 300 Ampere över 175 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.62V / 2.44%).
Hur stor effekt motsvarar 300A vid 230V?
Det motsvarar 69.0 kW med en rekommenderad säkring på 300A.
Related Lengths & Currents (230V)
300A · 5m (230V)300A · 10m (230V)300A · 15m (230V)300A · 20m (230V)300A · 25m (230V)300A · 30m (230V)300A · 35m (230V)300A · 40m (230V)300A · 45m (230V)300A · 50m (230V)300A · 60m (230V)300A · 70m (230V)10A · 175m (230V)16A · 175m (230V)20A · 175m (230V)25A · 175m (230V)32A · 175m (230V)40A · 175m (230V)50A · 175m (230V)63A · 175m (230V)80A · 175m (230V)100A · 175m (230V)125A · 175m (230V)160A · 175m (230V)200A · 175m (230V)