Kabelarea för 300 Ampere vid 45 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 300 A över 45 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 3.34V (0.83%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 3.44V (0.86%)
Voltage at Load396.7 VLine Loss: 1733.4 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A333.59 V (83.4%)66.4 V550.27 V (137.57%)173340.0 WDrop High
2.5 mm²24 A18 A200.16 V (50.04%)199.8 V330.16 V (82.54%)104004.0 WDrop High
4 mm²32 A25 A125.1 V (31.27%)274.9 V206.35 V (51.59%)65002.5 WDrop High
6 mm²41 A32 A83.4 V (20.85%)316.6 V137.57 V (34.39%)43335.0 WDrop High
10 mm²57 A44 A50.04 V (12.51%)350.0 V82.54 V (20.64%)26001.0 WDrop High
16 mm²76 A59 A31.27 V (7.82%)368.7 V51.59 V (12.9%)16250.6 WDrop High
25 mm²101 A78 A20.02 V (5.0%)380.0 V33.02 V (8.25%)10400.4 WDrop High
35 mm²125 A97 A14.3 V (3.57%)385.7 V23.58 V (5.9%)7428.9 WDrop High
50 mm²151 A118 A10.01 V (2.5%)390.0 V16.51 V (4.13%)5200.2 WDrop High
70 mm²192 A150 A7.15 V (1.79%)392.9 V11.79 V (2.95%)3714.4 WDrop High
95 mm²232 A181 A5.27 V (1.32%)394.7 V8.69 V (2.17%)2736.9 WDrop High
120 mm²269 A210 A4.17 V (1.04%)395.8 V6.88 V (1.72%)2166.7 WDrop High
150 mm²309 A241 A3.34 V (0.83%)396.7 V5.5 V (1.38%)1733.4 W✓ OK (≤3%)
185 mm²353 A275 A2.7 V (0.68%)397.3 V4.46 V (1.12%)1405.5 W✓ OK (≤3%)
240 mm²415 A324 A2.08 V (0.52%)397.9 V3.44 V (0.86%)1083.4 W✓ OK (≤3%)
300 mm²477 A372 A1.67 V (0.42%)398.3 V2.75 V (0.69%)866.7 W✓ OK (≤3%)
400 mm²570 A445 A1.25 V (0.31%)398.7 V2.06 V (0.52%)650.0 W✓ OK (≤3%)

FAQ — Kabelarea för 300 Ampere vid 45 Meter (400V)

Vilken kabelarea krävs för 300A vid 45 meter (400V)?

För 300 Ampere över 45 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (3.34V / 0.83%).

Hur stor effekt motsvarar 300A vid 400V?

Det motsvarar 207.85 kW med en rekommenderad säkring på 300A.