Kabelarea för 300 Ampere vid 5 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 300 A över 5 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 0.37V (0.09%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 0.38V (0.1%)
Voltage at Load399.6 VLine Loss: 192.6 W
Max Power & Breaker207.85 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A37.07 V (9.27%)362.9 V61.14 V (15.29%)19260.0 WDrop High
2.5 mm²24 A18 A22.24 V (5.56%)377.8 V36.68 V (9.17%)11556.0 WDrop High
4 mm²32 A25 A13.9 V (3.47%)386.1 V22.93 V (5.73%)7222.5 WDrop High
6 mm²41 A32 A9.27 V (2.32%)390.7 V15.29 V (3.82%)4815.0 WDrop High
10 mm²57 A44 A5.56 V (1.39%)394.4 V9.17 V (2.29%)2889.0 WDrop High
16 mm²76 A59 A3.47 V (0.87%)396.5 V5.73 V (1.43%)1805.6 WDrop High
25 mm²101 A78 A2.22 V (0.56%)397.8 V3.67 V (0.92%)1155.6 WDrop High
35 mm²125 A97 A1.59 V (0.4%)398.4 V2.62 V (0.66%)825.4 WDrop High
50 mm²151 A118 A1.11 V (0.28%)398.9 V1.83 V (0.46%)577.8 WDrop High
70 mm²192 A150 A0.79 V (0.2%)399.2 V1.31 V (0.33%)412.7 WDrop High
95 mm²232 A181 A0.59 V (0.15%)399.4 V0.97 V (0.24%)304.1 WDrop High
120 mm²269 A210 A0.46 V (0.12%)399.5 V0.76 V (0.19%)240.8 WDrop High
150 mm²309 A241 A0.37 V (0.09%)399.6 V0.61 V (0.15%)192.6 W✓ OK (≤3%)
185 mm²353 A275 A0.3 V (0.08%)399.7 V0.5 V (0.12%)156.2 W✓ OK (≤3%)
240 mm²415 A324 A0.23 V (0.06%)399.8 V0.38 V (0.1%)120.4 W✓ OK (≤3%)
300 mm²477 A372 A0.19 V (0.05%)399.8 V0.31 V (0.08%)96.3 W✓ OK (≤3%)
400 mm²570 A445 A0.14 V (0.03%)399.9 V0.23 V (0.06%)72.2 W✓ OK (≤3%)

FAQ — Kabelarea för 300 Ampere vid 5 Meter (400V)

Vilken kabelarea krävs för 300A vid 5 meter (400V)?

För 300 Ampere över 5 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (0.37V / 0.09%).

Hur stor effekt motsvarar 300A vid 400V?

Det motsvarar 207.85 kW med en rekommenderad säkring på 300A.