⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 300 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 300 A över 80 m vid 230V.

Copper Cable (≤3% Drop)150 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 5.65V (2.46%)
Voltage at Load223.2 VLine Loss: 2054.4 W
Max Power & Breaker69.0 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 300A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A684.8 V (297.74%)0.0 V1129.6 V (491.13%)205440.0 WDrop High
2.5 mm²24 A18 A410.88 V (178.64%)0.0 V677.76 V (294.68%)123264.0 WDrop High
4 mm²32 A25 A256.8 V (111.65%)0.0 V423.6 V (184.17%)77040.0 WDrop High
6 mm²41 A32 A171.2 V (74.43%)58.8 V282.4 V (122.78%)51360.0 WDrop High
10 mm²57 A44 A102.72 V (44.66%)127.3 V169.44 V (73.67%)30816.0 WDrop High
16 mm²76 A59 A64.2 V (27.91%)165.8 V105.9 V (46.04%)19260.0 WDrop High
25 mm²101 A78 A41.09 V (17.86%)188.9 V67.78 V (29.47%)12326.4 WDrop High
35 mm²125 A97 A29.35 V (12.76%)200.7 V48.41 V (21.05%)8804.6 WDrop High
50 mm²151 A118 A20.54 V (8.93%)209.5 V33.89 V (14.73%)6163.2 WDrop High
70 mm²192 A150 A14.67 V (6.38%)215.3 V24.21 V (10.52%)4402.3 WDrop High
95 mm²232 A181 A10.81 V (4.7%)219.2 V17.84 V (7.75%)3243.8 WDrop High
120 mm²269 A210 A8.56 V (3.72%)221.4 V14.12 V (6.14%)2568.0 WDrop High
150 mm²309 A241 A6.85 V (2.98%)223.2 V11.3 V (4.91%)2054.4 W✓ OK (≤3%)
185 mm²353 A275 A5.55 V (2.41%)224.4 V9.16 V (3.98%)1665.7 W✓ OK (≤3%)
240 mm²415 A324 A4.28 V (1.86%)225.7 V7.06 V (3.07%)1284.0 W✓ OK (≤3%)
300 mm²477 A372 A3.42 V (1.49%)226.6 V5.65 V (2.46%)1027.2 W✓ OK (≤3%)
400 mm²570 A445 A2.57 V (1.12%)227.4 V4.24 V (1.84%)770.4 W✓ OK (≤3%)

FAQ — Kabelarea för 300 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 300A vid 80 meter (230V)?

För 300 Ampere över 80 meter vid 230V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 300A vid 230V?

Det motsvarar 69.0 kW med en rekommenderad säkring på 300A.