Kabelarea för 32 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 200 m vid 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 5.48V (2.38%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.45V (2.81%)
Voltage at Load224.5 VLine Loss: 175.3 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A182.61 V (79.4%)47.4 V301.23 V (130.97%)5843.6 WDrop High
2.5 mm²24 A18 A109.57 V (47.64%)120.4 V180.74 V (78.58%)3506.2 WDrop High
4 mm²32 A25 A68.48 V (29.77%)161.5 V112.96 V (49.11%)2191.4 WDrop High
6 mm²41 A32 A45.65 V (19.85%)184.3 V75.31 V (32.74%)1460.9 WDrop High
10 mm²57 A44 A27.39 V (11.91%)202.6 V45.18 V (19.65%)876.5 WDrop High
16 mm²76 A59 A17.12 V (7.44%)212.9 V28.24 V (12.28%)547.8 WDrop High
25 mm²101 A78 A10.96 V (4.76%)219.0 V18.07 V (7.86%)350.6 W~ ≤5%
35 mm²125 A97 A7.83 V (3.4%)222.2 V12.91 V (5.61%)250.4 W~ ≤5%
50 mm²151 A118 A5.48 V (2.38%)224.5 V9.04 V (3.93%)175.3 W✓ OK (≤3%)
70 mm²192 A150 A3.91 V (1.7%)226.1 V6.45 V (2.81%)125.2 W✓ OK (≤3%)
95 mm²232 A181 A2.88 V (1.25%)227.1 V4.76 V (2.07%)92.3 W✓ OK (≤3%)
120 mm²269 A210 A2.28 V (0.99%)227.7 V3.77 V (1.64%)73.0 W✓ OK (≤3%)
150 mm²309 A241 A1.83 V (0.79%)228.2 V3.01 V (1.31%)58.4 W✓ OK (≤3%)
185 mm²353 A275 A1.48 V (0.64%)228.5 V2.44 V (1.06%)47.4 W✓ OK (≤3%)
240 mm²415 A324 A1.14 V (0.5%)228.9 V1.88 V (0.82%)36.5 W✓ OK (≤3%)
300 mm²477 A372 A0.91 V (0.4%)229.1 V1.51 V (0.65%)29.2 W✓ OK (≤3%)
400 mm²570 A445 A0.68 V (0.3%)229.3 V1.13 V (0.49%)21.9 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 32A vid 200 meter (230V)?

För 32 Ampere över 200 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (5.48V / 2.38%).

Hur stor effekt motsvarar 32A vid 230V?

Det motsvarar 7.36 kW med en rekommenderad säkring på 32A.