Kabelarea för 80 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 80 A över 200 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.11V (2.65%)
Voltage at Load224.3 VLine Loss: 456.5 W
Max Power & Breaker18.4 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A456.53 V (198.49%)0.0 V753.07 V (327.42%)36522.7 WDrop High
2.5 mm²24 A18 A273.92 V (119.1%)0.0 V451.84 V (196.45%)21913.6 WDrop High
4 mm²32 A25 A171.2 V (74.43%)58.8 V282.4 V (122.78%)13696.0 WDrop High
6 mm²41 A32 A114.13 V (49.62%)115.9 V188.27 V (81.86%)9130.7 WDrop High
10 mm²57 A44 A68.48 V (29.77%)161.5 V112.96 V (49.11%)5478.4 WDrop High
16 mm²76 A59 A42.8 V (18.61%)187.2 V70.6 V (30.7%)3424.0 WDrop High
25 mm²101 A78 A27.39 V (11.91%)202.6 V45.18 V (19.65%)2191.4 WDrop High
35 mm²125 A97 A19.57 V (8.51%)210.4 V32.27 V (14.03%)1565.3 WDrop High
50 mm²151 A118 A13.7 V (5.95%)216.3 V22.59 V (9.82%)1095.7 WDrop High
70 mm²192 A150 A9.78 V (4.25%)220.2 V16.14 V (7.02%)782.6 W~ ≤5%
95 mm²232 A181 A7.21 V (3.13%)222.8 V11.89 V (5.17%)576.7 W~ ≤5%
120 mm²269 A210 A5.71 V (2.48%)224.3 V9.41 V (4.09%)456.5 W✓ OK (≤3%)
150 mm²309 A241 A4.57 V (1.98%)225.4 V7.53 V (3.27%)365.2 W✓ OK (≤3%)
185 mm²353 A275 A3.7 V (1.61%)226.3 V6.11 V (2.65%)296.1 W✓ OK (≤3%)
240 mm²415 A324 A2.85 V (1.24%)227.1 V4.71 V (2.05%)228.3 W✓ OK (≤3%)
300 mm²477 A372 A2.28 V (0.99%)227.7 V3.77 V (1.64%)182.6 W✓ OK (≤3%)
400 mm²570 A445 A1.71 V (0.74%)228.3 V2.82 V (1.23%)137.0 W✓ OK (≤3%)

FAQ — Kabelarea för 80 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 80A vid 200 meter (230V)?

För 80 Ampere över 200 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (5.71V / 2.48%).

Hur stor effekt motsvarar 80A vid 230V?

Det motsvarar 18.4 kW med en rekommenderad säkring på 80A.