⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 40 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 200 m vid 230V.

Copper Cable (≤3% Drop)50 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 5.95V (2.58%)
Voltage at Load223.2 VLine Loss: 273.9 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A228.27 V (99.25%)1.7 V376.53 V (163.71%)9130.7 WDrop High
2.5 mm²24 A18 A136.96 V (59.55%)93.0 V225.92 V (98.23%)5478.4 WDrop High
4 mm²32 A25 A85.6 V (37.22%)144.4 V141.2 V (61.39%)3424.0 WDrop High
6 mm²41 A32 A57.07 V (24.81%)172.9 V94.13 V (40.93%)2282.7 WDrop High
10 mm²57 A44 A34.24 V (14.89%)195.8 V56.48 V (24.56%)1369.6 WDrop High
16 mm²76 A59 A21.4 V (9.3%)208.6 V35.3 V (15.35%)856.0 WDrop High
25 mm²101 A78 A13.7 V (5.95%)216.3 V22.59 V (9.82%)547.8 WDrop High
35 mm²125 A97 A9.78 V (4.25%)220.2 V16.14 V (7.02%)391.3 W~ ≤5%
50 mm²151 A118 A6.85 V (2.98%)223.2 V11.3 V (4.91%)273.9 W✓ OK (≤3%)
70 mm²192 A150 A4.89 V (2.13%)225.1 V8.07 V (3.51%)195.7 W✓ OK (≤3%)
95 mm²232 A181 A3.6 V (1.57%)226.4 V5.95 V (2.58%)144.2 W✓ OK (≤3%)
120 mm²269 A210 A2.85 V (1.24%)227.1 V4.71 V (2.05%)114.1 W✓ OK (≤3%)
150 mm²309 A241 A2.28 V (0.99%)227.7 V3.77 V (1.64%)91.3 W✓ OK (≤3%)
185 mm²353 A275 A1.85 V (0.8%)228.1 V3.05 V (1.33%)74.0 W✓ OK (≤3%)
240 mm²415 A324 A1.43 V (0.62%)228.6 V2.35 V (1.02%)57.1 W✓ OK (≤3%)
300 mm²477 A372 A1.14 V (0.5%)228.9 V1.88 V (0.82%)45.7 W✓ OK (≤3%)
400 mm²570 A445 A0.86 V (0.37%)229.1 V1.41 V (0.61%)34.2 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 40A vid 200 meter (230V)?

För 40 Ampere över 200 meter vid 230V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 40A vid 230V?

Det motsvarar 9.2 kW med en rekommenderad säkring på 40A.