⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 32 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 30 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 9.78V (2.45%)
Voltage at Load391.1 VLine Loss: 493.1 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A23.72 V (5.93%)376.3 V39.13 V (9.78%)1314.8 WDrop High
2.5 mm²24 A18 A14.23 V (3.56%)385.8 V23.48 V (5.87%)788.9 WDrop High
4 mm²32 A25 A8.9 V (2.22%)391.1 V14.67 V (3.67%)493.1 W✓ OK (≤3%)
6 mm²41 A32 A5.93 V (1.48%)394.1 V9.78 V (2.45%)328.7 W✓ OK (≤3%)
10 mm²57 A44 A3.56 V (0.89%)396.4 V5.87 V (1.47%)197.2 W✓ OK (≤3%)
16 mm²76 A59 A2.22 V (0.56%)397.8 V3.67 V (0.92%)123.3 W✓ OK (≤3%)
25 mm²101 A78 A1.42 V (0.36%)398.6 V2.35 V (0.59%)78.9 W✓ OK (≤3%)
35 mm²125 A97 A1.02 V (0.25%)399.0 V1.68 V (0.42%)56.3 W✓ OK (≤3%)
50 mm²151 A118 A0.71 V (0.18%)399.3 V1.17 V (0.29%)39.4 W✓ OK (≤3%)
70 mm²192 A150 A0.51 V (0.13%)399.5 V0.84 V (0.21%)28.2 W✓ OK (≤3%)
95 mm²232 A181 A0.37 V (0.09%)399.6 V0.62 V (0.15%)20.8 W✓ OK (≤3%)
120 mm²269 A210 A0.3 V (0.07%)399.7 V0.49 V (0.12%)16.4 W✓ OK (≤3%)
150 mm²309 A241 A0.24 V (0.06%)399.8 V0.39 V (0.1%)13.1 W✓ OK (≤3%)
185 mm²353 A275 A0.19 V (0.05%)399.8 V0.32 V (0.08%)10.7 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)399.9 V0.24 V (0.06%)8.2 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)399.9 V0.2 V (0.05%)6.6 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)399.9 V0.15 V (0.04%)4.9 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 32A vid 30 meter (400V)?

För 32 Ampere över 30 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (8.9V / 2.22%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.