⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 125 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 30 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 3.97V (0.99%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 3.28V (0.82%)
Voltage at Load396.0 VLine Loss: 859.8 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A92.66 V (23.17%)307.3 V152.85 V (38.21%)20062.5 WDrop High
2.5 mm²24 A18 A55.6 V (13.9%)344.4 V91.71 V (22.93%)12037.5 WDrop High
4 mm²32 A25 A34.75 V (8.69%)365.3 V57.32 V (14.33%)7523.4 WDrop High
6 mm²41 A32 A23.17 V (5.79%)376.8 V38.21 V (9.55%)5015.6 WDrop High
10 mm²57 A44 A13.9 V (3.47%)386.1 V22.93 V (5.73%)3009.4 WDrop High
16 mm²76 A59 A8.69 V (2.17%)391.3 V14.33 V (3.58%)1880.9 WDrop High
25 mm²101 A78 A5.56 V (1.39%)394.4 V9.17 V (2.29%)1203.8 WDrop High
35 mm²125 A97 A3.97 V (0.99%)396.0 V6.55 V (1.64%)859.8 W✓ OK (≤3%)
50 mm²151 A118 A2.78 V (0.69%)397.2 V4.59 V (1.15%)601.9 W✓ OK (≤3%)
70 mm²192 A150 A1.99 V (0.5%)398.0 V3.28 V (0.82%)429.9 W✓ OK (≤3%)
95 mm²232 A181 A1.46 V (0.37%)398.5 V2.41 V (0.6%)316.8 W✓ OK (≤3%)
120 mm²269 A210 A1.16 V (0.29%)398.8 V1.91 V (0.48%)250.8 W✓ OK (≤3%)
150 mm²309 A241 A0.93 V (0.23%)399.1 V1.53 V (0.38%)200.6 W✓ OK (≤3%)
185 mm²353 A275 A0.75 V (0.19%)399.2 V1.24 V (0.31%)162.7 W✓ OK (≤3%)
240 mm²415 A324 A0.58 V (0.14%)399.4 V0.96 V (0.24%)125.4 W✓ OK (≤3%)
300 mm²477 A372 A0.46 V (0.12%)399.5 V0.76 V (0.19%)100.3 W✓ OK (≤3%)
400 mm²570 A445 A0.35 V (0.09%)399.7 V0.57 V (0.14%)75.2 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 125A vid 30 meter (400V)?

För 125 Ampere över 30 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (3.97V / 0.99%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.