⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 32 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 10 m vid 400V.

Copper Cable (≤3% Drop)4 mm²Drop: 2.97V (0.74%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 3.26V (0.82%)
Voltage at Load397.0 VLine Loss: 164.4 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.91 V (1.98%)392.1 V13.04 V (3.26%)438.3 WDrop High
2.5 mm²24 A18 A4.74 V (1.19%)395.3 V7.83 V (1.96%)263.0 WDrop High
4 mm²32 A25 A2.97 V (0.74%)397.0 V4.89 V (1.22%)164.4 W✓ OK (≤3%)
6 mm²41 A32 A1.98 V (0.49%)398.0 V3.26 V (0.82%)109.6 W✓ OK (≤3%)
10 mm²57 A44 A1.19 V (0.3%)398.8 V1.96 V (0.49%)65.7 W✓ OK (≤3%)
16 mm²76 A59 A0.74 V (0.19%)399.3 V1.22 V (0.31%)41.1 W✓ OK (≤3%)
25 mm²101 A78 A0.47 V (0.12%)399.5 V0.78 V (0.2%)26.3 W✓ OK (≤3%)
35 mm²125 A97 A0.34 V (0.08%)399.7 V0.56 V (0.14%)18.8 W✓ OK (≤3%)
50 mm²151 A118 A0.24 V (0.06%)399.8 V0.39 V (0.1%)13.1 W✓ OK (≤3%)
70 mm²192 A150 A0.17 V (0.04%)399.8 V0.28 V (0.07%)9.4 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.03%)399.9 V0.21 V (0.05%)6.9 W✓ OK (≤3%)
120 mm²269 A210 A0.1 V (0.02%)399.9 V0.16 V (0.04%)5.5 W✓ OK (≤3%)
150 mm²309 A241 A0.08 V (0.02%)399.9 V0.13 V (0.03%)4.4 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.02%)399.9 V0.11 V (0.03%)3.6 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)400.0 V0.08 V (0.02%)2.7 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)400.0 V0.07 V (0.02%)2.2 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.01%)400.0 V0.05 V (0.01%)1.6 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 32A vid 10 meter (400V)?

För 32 Ampere över 10 meter vid 400V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (2.97V / 0.74%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.