Kabelarea för 32 Ampere vid 400 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 400 m vid 400V.
Copper Cable (≤3% Drop)50 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 11.18V (2.8%)
Voltage at Load390.5 VLine Loss: 525.9 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 400m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 316.3 V (79.07%) | 83.7 V | 521.74 V (130.43%) | 17530.9 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 189.78 V (47.44%) | 210.2 V | 313.04 V (78.26%) | 10518.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 118.61 V (29.65%) | 281.4 V | 195.65 V (48.91%) | 6574.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 79.07 V (19.77%) | 320.9 V | 130.43 V (32.61%) | 4382.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 47.44 V (11.86%) | 352.6 V | 78.26 V (19.57%) | 2629.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 1643.5 W | Drop High |
| 25 mm² | 101 A | 78 A | 18.98 V (4.74%) | 381.0 V | 31.3 V (7.83%) | 1051.9 W | ~ ≤5% |
| 35 mm² | 125 A | 97 A | 13.56 V (3.39%) | 386.4 V | 22.36 V (5.59%) | 751.3 W | ~ ≤5% |
| 50 mm² | 151 A | 118 A | 9.49 V (2.37%) | 390.5 V | 15.65 V (3.91%) | 525.9 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 6.78 V (1.69%) | 393.2 V | 11.18 V (2.8%) | 375.7 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 4.99 V (1.25%) | 395.0 V | 8.24 V (2.06%) | 276.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 3.95 V (0.99%) | 396.0 V | 6.52 V (1.63%) | 219.1 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 3.16 V (0.79%) | 396.8 V | 5.22 V (1.3%) | 175.3 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.56 V (0.64%) | 397.4 V | 4.23 V (1.06%) | 142.1 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.98 V (0.49%) | 398.0 V | 3.26 V (0.82%) | 109.6 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.58 V (0.4%) | 398.4 V | 2.61 V (0.65%) | 87.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 65.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 32 Ampere vid 400 Meter (400V)
Vilken kabelarea krävs för 32A vid 400 meter (400V)?
För 32 Ampere över 400 meter vid 400V rekommenderas 50 mm² kopparkabel för att hålla spänningsfallet under 3% (9.49V / 2.37%).
Hur stor effekt motsvarar 32A vid 400V?
Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 400m (400V)16A · 400m (400V)20A · 400m (400V)25A · 400m (400V)40A · 400m (400V)50A · 400m (400V)63A · 400m (400V)80A · 400m (400V)100A · 400m (400V)125A · 400m (400V)160A · 400m (400V)200A · 400m (400V)