Kabelarea för 32 Ampere vid 600 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 600 m vid 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 5.65V (2.46%)
Voltage at Load223.2 VLine Loss: 219.1 W
Max Power & Breaker7.36 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A547.84 V (238.19%)0.0 V903.68 V (392.9%)17530.9 WDrop High
2.5 mm²24 A18 A328.7 V (142.91%)0.0 V542.21 V (235.74%)10518.5 WDrop High
4 mm²32 A25 A205.44 V (89.32%)24.6 V338.88 V (147.34%)6574.1 WDrop High
6 mm²41 A32 A136.96 V (59.55%)93.0 V225.92 V (98.23%)4382.7 WDrop High
10 mm²57 A44 A82.18 V (35.73%)147.8 V135.55 V (58.94%)2629.6 WDrop High
16 mm²76 A59 A51.36 V (22.33%)178.6 V84.72 V (36.83%)1643.5 WDrop High
25 mm²101 A78 A32.87 V (14.29%)197.1 V54.22 V (23.57%)1051.9 WDrop High
35 mm²125 A97 A23.48 V (10.21%)206.5 V38.73 V (16.84%)751.3 WDrop High
50 mm²151 A118 A16.44 V (7.15%)213.6 V27.11 V (11.79%)525.9 WDrop High
70 mm²192 A150 A11.74 V (5.1%)218.3 V19.36 V (8.42%)375.7 WDrop High
95 mm²232 A181 A8.65 V (3.76%)221.3 V14.27 V (6.2%)276.8 W~ ≤5%
120 mm²269 A210 A6.85 V (2.98%)223.2 V11.3 V (4.91%)219.1 W✓ OK (≤3%)
150 mm²309 A241 A5.48 V (2.38%)224.5 V9.04 V (3.93%)175.3 W✓ OK (≤3%)
185 mm²353 A275 A4.44 V (1.93%)225.6 V7.33 V (3.19%)142.1 W✓ OK (≤3%)
240 mm²415 A324 A3.42 V (1.49%)226.6 V5.65 V (2.46%)109.6 W✓ OK (≤3%)
300 mm²477 A372 A2.74 V (1.19%)227.3 V4.52 V (1.96%)87.7 W✓ OK (≤3%)
400 mm²570 A445 A2.05 V (0.89%)227.9 V3.39 V (1.47%)65.7 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 600 Meter (230V)

Vilken kabelarea krävs för 32A vid 600 meter (230V)?

För 32 Ampere över 600 meter vid 230V rekommenderas 120 mm² kopparkabel för att hålla spänningsfallet under 3% (6.85V / 2.98%).

Hur stor effekt motsvarar 32A vid 230V?

Det motsvarar 7.36 kW med en rekommenderad säkring på 32A.