Kabelarea för 63 Ampere vid 600 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 600 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.67V (2.9%)
Voltage at Load223.3 VLine Loss: 424.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1078.56 V (468.94%)0.0 V1779.12 V (773.53%)67949.3 WDrop High
2.5 mm²24 A18 A647.14 V (281.36%)0.0 V1067.47 V (464.12%)40769.6 WDrop High
4 mm²32 A25 A404.46 V (175.85%)0.0 V667.17 V (290.07%)25481.0 WDrop High
6 mm²41 A32 A269.64 V (117.23%)0.0 V444.78 V (193.38%)16987.3 WDrop High
10 mm²57 A44 A161.78 V (70.34%)68.2 V266.87 V (116.03%)10192.4 WDrop High
16 mm²76 A59 A101.11 V (43.96%)128.9 V166.79 V (72.52%)6370.2 WDrop High
25 mm²101 A78 A64.71 V (28.14%)165.3 V106.75 V (46.41%)4077.0 WDrop High
35 mm²125 A97 A46.22 V (20.1%)183.8 V76.25 V (33.15%)2912.1 WDrop High
50 mm²151 A118 A32.36 V (14.07%)197.6 V53.37 V (23.21%)2038.5 WDrop High
70 mm²192 A150 A23.11 V (10.05%)206.9 V38.12 V (16.58%)1456.1 WDrop High
95 mm²232 A181 A17.03 V (7.4%)213.0 V28.09 V (12.21%)1072.9 WDrop High
120 mm²269 A210 A13.48 V (5.86%)216.5 V22.24 V (9.67%)849.4 WDrop High
150 mm²309 A241 A10.79 V (4.69%)219.2 V17.79 V (7.74%)679.5 W~ ≤5%
185 mm²353 A275 A8.75 V (3.8%)221.3 V14.43 V (6.27%)550.9 W~ ≤5%
240 mm²415 A324 A6.74 V (2.93%)223.3 V11.12 V (4.83%)424.7 W✓ OK (≤3%)
300 mm²477 A372 A5.39 V (2.34%)224.6 V8.9 V (3.87%)339.7 W✓ OK (≤3%)
400 mm²570 A445 A4.04 V (1.76%)226.0 V6.67 V (2.9%)254.8 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 600 Meter (230V)

Vilken kabelarea krävs för 63A vid 600 meter (230V)?

För 63 Ampere över 600 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.