⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 125 Ampere vid 600 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 600 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 4.01V (1.75%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 13.24V (5.76%)
Voltage at Load226.0 VLine Loss: 501.6 W
Max Power & Breaker28.75 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2140.0 V (930.43%)0.0 V3530.0 V (1534.78%)267500.0 WDrop High
2.5 mm²24 A18 A1284.0 V (558.26%)0.0 V2118.0 V (920.87%)160500.0 WDrop High
4 mm²32 A25 A802.5 V (348.91%)0.0 V1323.75 V (575.54%)100312.5 WDrop High
6 mm²41 A32 A535.0 V (232.61%)0.0 V882.5 V (383.7%)66875.0 WDrop High
10 mm²57 A44 A321.0 V (139.57%)0.0 V529.5 V (230.22%)40125.0 WDrop High
16 mm²76 A59 A200.62 V (87.23%)29.4 V330.94 V (143.89%)25078.1 WDrop High
25 mm²101 A78 A128.4 V (55.83%)101.6 V211.8 V (92.09%)16050.0 WDrop High
35 mm²125 A97 A91.71 V (39.88%)138.3 V151.29 V (65.78%)11464.3 WDrop High
50 mm²151 A118 A64.2 V (27.91%)165.8 V105.9 V (46.04%)8025.0 WDrop High
70 mm²192 A150 A45.86 V (19.94%)184.1 V75.64 V (32.89%)5732.1 WDrop High
95 mm²232 A181 A33.79 V (14.69%)196.2 V55.74 V (24.23%)4223.7 WDrop High
120 mm²269 A210 A26.75 V (11.63%)203.2 V44.12 V (19.18%)3343.8 WDrop High
150 mm²309 A241 A21.4 V (9.3%)208.6 V35.3 V (15.35%)2675.0 WDrop High
185 mm²353 A275 A17.35 V (7.54%)212.6 V28.62 V (12.44%)2168.9 WDrop High
240 mm²415 A324 A13.38 V (5.82%)216.6 V22.06 V (9.59%)1671.9 WDrop High
300 mm²477 A372 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1337.5 W~ ≤5%
400 mm²570 A445 A8.02 V (3.49%)222.0 V13.24 V (5.76%)1003.1 W~ ≤5%

FAQ — Kabelarea för 125 Ampere vid 600 Meter (230V)

Vilken kabelarea krävs för 125A vid 600 meter (230V)?

För 125 Ampere över 600 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (4.01V / 1.75%).

Hur stor effekt motsvarar 125A vid 230V?

Det motsvarar 28.75 kW med en rekommenderad säkring på 125A.