⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 325 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 25 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 1.63V (0.41%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 1.66V (0.41%)
Voltage at Load398.4 VLine Loss: 916.4 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A200.77 V (50.19%)199.2 V331.18 V (82.8%)113018.7 WDrop High
2.5 mm²24 A18 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
4 mm²32 A25 A75.29 V (18.82%)324.7 V124.19 V (31.05%)42382.0 WDrop High
6 mm²41 A32 A50.19 V (12.55%)349.8 V82.8 V (20.7%)28254.7 WDrop High
10 mm²57 A44 A30.12 V (7.53%)369.9 V49.68 V (12.42%)16952.8 WDrop High
16 mm²76 A59 A18.82 V (4.71%)381.2 V31.05 V (7.76%)10595.5 WDrop High
25 mm²101 A78 A12.05 V (3.01%)388.0 V19.87 V (4.97%)6781.1 WDrop High
35 mm²125 A97 A8.6 V (2.15%)391.4 V14.19 V (3.55%)4843.7 WDrop High
50 mm²151 A118 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 WDrop High
70 mm²192 A150 A4.3 V (1.08%)395.7 V7.1 V (1.77%)2421.8 WDrop High
95 mm²232 A181 A3.17 V (0.79%)396.8 V5.23 V (1.31%)1784.5 WDrop High
120 mm²269 A210 A2.51 V (0.63%)397.5 V4.14 V (1.03%)1412.7 WDrop High
150 mm²309 A241 A2.01 V (0.5%)398.0 V3.31 V (0.83%)1130.2 WDrop High
185 mm²353 A275 A1.63 V (0.41%)398.4 V2.69 V (0.67%)916.4 W✓ OK (≤3%)
240 mm²415 A324 A1.25 V (0.31%)398.7 V2.07 V (0.52%)706.4 W✓ OK (≤3%)
300 mm²477 A372 A1.0 V (0.25%)399.0 V1.66 V (0.41%)565.1 W✓ OK (≤3%)
400 mm²570 A445 A0.75 V (0.19%)399.2 V1.24 V (0.31%)423.8 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 325A vid 25 meter (400V)?

För 325 Ampere över 25 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (1.63V / 0.41%).

Hur stor effekt motsvarar 325A vid 400V?

Det motsvarar 225.17 kW med en rekommenderad säkring på 350A.