Kabelarea för 325 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 60 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 3.91V (0.98%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 3.97V (0.99%)
Voltage at Load396.1 VLine Loss: 2199.3 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A481.86 V (120.46%)0.0 V794.84 V (198.71%)271245.0 WDrop High
2.5 mm²24 A18 A289.11 V (72.28%)110.9 V476.9 V (119.23%)162747.0 WDrop High
4 mm²32 A25 A180.7 V (45.17%)219.3 V298.06 V (74.52%)101716.9 WDrop High
6 mm²41 A32 A120.46 V (30.12%)279.5 V198.71 V (49.68%)67811.2 WDrop High
10 mm²57 A44 A72.28 V (18.07%)327.7 V119.23 V (29.81%)40686.8 WDrop High
16 mm²76 A59 A45.17 V (11.29%)354.8 V74.52 V (18.63%)25429.2 WDrop High
25 mm²101 A78 A28.91 V (7.23%)371.1 V47.69 V (11.92%)16274.7 WDrop High
35 mm²125 A97 A20.65 V (5.16%)379.3 V34.06 V (8.52%)11624.8 WDrop High
50 mm²151 A118 A14.46 V (3.61%)385.5 V23.85 V (5.96%)8137.4 WDrop High
70 mm²192 A150 A10.33 V (2.58%)389.7 V17.03 V (4.26%)5812.4 WDrop High
95 mm²232 A181 A7.61 V (1.9%)392.4 V12.55 V (3.14%)4282.8 WDrop High
120 mm²269 A210 A6.02 V (1.51%)394.0 V9.94 V (2.48%)3390.6 WDrop High
150 mm²309 A241 A4.82 V (1.2%)395.2 V7.95 V (1.99%)2712.4 WDrop High
185 mm²353 A275 A3.91 V (0.98%)396.1 V6.44 V (1.61%)2199.3 W✓ OK (≤3%)
240 mm²415 A324 A3.01 V (0.75%)397.0 V4.97 V (1.24%)1695.3 W✓ OK (≤3%)
300 mm²477 A372 A2.41 V (0.6%)397.6 V3.97 V (0.99%)1356.2 W✓ OK (≤3%)
400 mm²570 A445 A1.81 V (0.45%)398.2 V2.98 V (0.75%)1017.2 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 325A vid 60 meter (400V)?

För 325 Ampere över 60 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (3.91V / 0.98%).

Hur stor effekt motsvarar 325A vid 400V?

Det motsvarar 225.17 kW med en rekommenderad säkring på 350A.