Kabelarea för 63 Ampere vid 70 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 70 m vid 230V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.39V (2.34%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.23V (2.71%)
Voltage at Load224.6 VLine Loss: 339.7 W
Max Power & Breaker14.49 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A125.83 V (54.71%)104.2 V207.56 V (90.25%)7927.4 WDrop High
2.5 mm²24 A18 A75.5 V (32.83%)154.5 V124.54 V (54.15%)4756.4 WDrop High
4 mm²32 A25 A47.19 V (20.52%)182.8 V77.84 V (33.84%)2972.8 WDrop High
6 mm²41 A32 A31.46 V (13.68%)198.5 V51.89 V (22.56%)1981.9 WDrop High
10 mm²57 A44 A18.87 V (8.21%)211.1 V31.13 V (13.54%)1189.1 WDrop High
16 mm²76 A59 A11.8 V (5.13%)218.2 V19.46 V (8.46%)743.2 WDrop High
25 mm²101 A78 A7.55 V (3.28%)222.5 V12.45 V (5.41%)475.6 W~ ≤5%
35 mm²125 A97 A5.39 V (2.34%)224.6 V8.9 V (3.87%)339.7 W✓ OK (≤3%)
50 mm²151 A118 A3.77 V (1.64%)226.2 V6.23 V (2.71%)237.8 W✓ OK (≤3%)
70 mm²192 A150 A2.7 V (1.17%)227.3 V4.45 V (1.93%)169.9 W✓ OK (≤3%)
95 mm²232 A181 A1.99 V (0.86%)228.0 V3.28 V (1.42%)125.2 W✓ OK (≤3%)
120 mm²269 A210 A1.57 V (0.68%)228.4 V2.59 V (1.13%)99.1 W✓ OK (≤3%)
150 mm²309 A241 A1.26 V (0.55%)228.7 V2.08 V (0.9%)79.3 W✓ OK (≤3%)
185 mm²353 A275 A1.02 V (0.44%)229.0 V1.68 V (0.73%)64.3 W✓ OK (≤3%)
240 mm²415 A324 A0.79 V (0.34%)229.2 V1.3 V (0.56%)49.5 W✓ OK (≤3%)
300 mm²477 A372 A0.63 V (0.27%)229.4 V1.04 V (0.45%)39.6 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.21%)229.5 V0.78 V (0.34%)29.7 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 70 Meter (230V)

Vilken kabelarea krävs för 63A vid 70 meter (230V)?

För 63 Ampere över 70 meter vid 230V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (5.39V / 2.34%).

Hur stor effekt motsvarar 63A vid 230V?

Det motsvarar 14.49 kW med en rekommenderad säkring på 63A.