Kabelarea för 35 Ampere vid 45 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 45 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 6.74V (2.93%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 4.45V (1.93%)
Voltage at Load223.3 VLine Loss: 235.9 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A44.94 V (19.54%)185.1 V74.13 V (32.23%)1572.9 WDrop High
2.5 mm²24 A18 A26.96 V (11.72%)203.0 V44.48 V (19.34%)943.7 WDrop High
4 mm²32 A25 A16.85 V (7.33%)213.1 V27.8 V (12.09%)589.8 WDrop High
6 mm²41 A32 A11.23 V (4.88%)218.8 V18.53 V (8.06%)393.2 W~ ≤5%
10 mm²57 A44 A6.74 V (2.93%)223.3 V11.12 V (4.83%)235.9 W✓ OK (≤3%)
16 mm²76 A59 A4.21 V (1.83%)225.8 V6.95 V (3.02%)147.5 W✓ OK (≤3%)
25 mm²101 A78 A2.7 V (1.17%)227.3 V4.45 V (1.93%)94.4 W✓ OK (≤3%)
35 mm²125 A97 A1.93 V (0.84%)228.1 V3.18 V (1.38%)67.4 W✓ OK (≤3%)
50 mm²151 A118 A1.35 V (0.59%)228.7 V2.22 V (0.97%)47.2 W✓ OK (≤3%)
70 mm²192 A150 A0.96 V (0.42%)229.0 V1.59 V (0.69%)33.7 W✓ OK (≤3%)
95 mm²232 A181 A0.71 V (0.31%)229.3 V1.17 V (0.51%)24.8 W✓ OK (≤3%)
120 mm²269 A210 A0.56 V (0.24%)229.4 V0.93 V (0.4%)19.7 W✓ OK (≤3%)
150 mm²309 A241 A0.45 V (0.2%)229.6 V0.74 V (0.32%)15.7 W✓ OK (≤3%)
185 mm²353 A275 A0.36 V (0.16%)229.6 V0.6 V (0.26%)12.8 W✓ OK (≤3%)
240 mm²415 A324 A0.28 V (0.12%)229.7 V0.46 V (0.2%)9.8 W✓ OK (≤3%)
300 mm²477 A372 A0.22 V (0.1%)229.8 V0.37 V (0.16%)7.9 W✓ OK (≤3%)
400 mm²570 A445 A0.17 V (0.07%)229.8 V0.28 V (0.12%)5.9 W✓ OK (≤3%)

FAQ — Kabelarea för 35 Ampere vid 45 Meter (230V)

Vilken kabelarea krävs för 35A vid 45 meter (230V)?

För 35 Ampere över 45 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (6.74V / 2.93%).

Hur stor effekt motsvarar 35A vid 230V?

Det motsvarar 8.05 kW med en rekommenderad säkring på 35A.