Kabelarea för 35 Ampere vid 15 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 15 m vid 230V.

Copper Cable (≤3% Drop)6 mm²Drop: 3.75V (1.63%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 3.71V (1.61%)
Voltage at Load226.3 VLine Loss: 131.1 W
Max Power & Breaker8.05 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.98 V (6.51%)215.0 V24.71 V (10.74%)524.3 WDrop High
2.5 mm²24 A18 A8.99 V (3.91%)221.0 V14.83 V (6.45%)314.6 WDrop High
4 mm²32 A25 A5.62 V (2.44%)224.4 V9.27 V (4.03%)196.6 WDrop High
6 mm²41 A32 A3.75 V (1.63%)226.3 V6.18 V (2.69%)131.1 W✓ OK (≤3%)
10 mm²57 A44 A2.25 V (0.98%)227.8 V3.71 V (1.61%)78.6 W✓ OK (≤3%)
16 mm²76 A59 A1.4 V (0.61%)228.6 V2.32 V (1.01%)49.2 W✓ OK (≤3%)
25 mm²101 A78 A0.9 V (0.39%)229.1 V1.48 V (0.64%)31.5 W✓ OK (≤3%)
35 mm²125 A97 A0.64 V (0.28%)229.4 V1.06 V (0.46%)22.5 W✓ OK (≤3%)
50 mm²151 A118 A0.45 V (0.2%)229.6 V0.74 V (0.32%)15.7 W✓ OK (≤3%)
70 mm²192 A150 A0.32 V (0.14%)229.7 V0.53 V (0.23%)11.2 W✓ OK (≤3%)
95 mm²232 A181 A0.24 V (0.1%)229.8 V0.39 V (0.17%)8.3 W✓ OK (≤3%)
120 mm²269 A210 A0.19 V (0.08%)229.8 V0.31 V (0.13%)6.6 W✓ OK (≤3%)
150 mm²309 A241 A0.15 V (0.07%)229.9 V0.25 V (0.11%)5.2 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.05%)229.9 V0.2 V (0.09%)4.3 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.15 V (0.07%)3.3 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.12 V (0.05%)2.6 W✓ OK (≤3%)
400 mm²570 A445 A0.06 V (0.02%)229.9 V0.09 V (0.04%)2.0 W✓ OK (≤3%)

FAQ — Kabelarea för 35 Ampere vid 15 Meter (230V)

Vilken kabelarea krävs för 35A vid 15 meter (230V)?

För 35 Ampere över 15 meter vid 230V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (3.75V / 1.63%).

Hur stor effekt motsvarar 35A vid 230V?

Det motsvarar 8.05 kW med en rekommenderad säkring på 35A.