Kabelarea för 35 Ampere vid 70 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 70 m vid 230V.
Copper Cable (≤3% Drop)16 mm²Drop: 6.55V (2.85%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 4.94V (2.15%)
Voltage at Load223.4 VLine Loss: 229.4 W
Max Power & Breaker8.05 kW35A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 70m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 69.91 V (30.39%) | 160.1 V | 115.31 V (50.14%) | 2446.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 41.94 V (18.24%) | 188.1 V | 69.19 V (30.08%) | 1468.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 26.21 V (11.4%) | 203.8 V | 43.24 V (18.8%) | 917.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 17.48 V (7.6%) | 212.5 V | 28.83 V (12.53%) | 611.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 10.49 V (4.56%) | 219.5 V | 17.3 V (7.52%) | 367.0 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 6.55 V (2.85%) | 223.4 V | 10.81 V (4.7%) | 229.4 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 4.19 V (1.82%) | 225.8 V | 6.92 V (3.01%) | 146.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 3.0 V (1.3%) | 227.0 V | 4.94 V (2.15%) | 104.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.1 V (0.91%) | 227.9 V | 3.46 V (1.5%) | 73.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.5 V (0.65%) | 228.5 V | 2.47 V (1.07%) | 52.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.1 V (0.48%) | 228.9 V | 1.82 V (0.79%) | 38.6 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.87 V (0.38%) | 229.1 V | 1.44 V (0.63%) | 30.6 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.7 V (0.3%) | 229.3 V | 1.15 V (0.5%) | 24.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.57 V (0.25%) | 229.4 V | 0.93 V (0.41%) | 19.8 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.44 V (0.19%) | 229.6 V | 0.72 V (0.31%) | 15.3 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.35 V (0.15%) | 229.7 V | 0.58 V (0.25%) | 12.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.26 V (0.11%) | 229.7 V | 0.43 V (0.19%) | 9.2 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 35 Ampere vid 70 Meter (230V)
Vilken kabelarea krävs för 35A vid 70 meter (230V)?
För 35 Ampere över 70 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (6.55V / 2.85%).
Hur stor effekt motsvarar 35A vid 230V?
Det motsvarar 8.05 kW med en rekommenderad säkring på 35A.
Related Lengths & Currents (230V)
35A · 5m (230V)35A · 10m (230V)35A · 15m (230V)35A · 20m (230V)35A · 25m (230V)35A · 30m (230V)35A · 35m (230V)35A · 40m (230V)35A · 45m (230V)35A · 50m (230V)35A · 60m (230V)10A · 70m (230V)16A · 70m (230V)20A · 70m (230V)25A · 70m (230V)32A · 70m (230V)40A · 70m (230V)50A · 70m (230V)63A · 70m (230V)80A · 70m (230V)100A · 70m (230V)125A · 70m (230V)160A · 70m (230V)200A · 70m (230V)