Kabelarea för 35 Ampere vid 70 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 70 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 9.08V (2.27%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.36V (2.34%)
Voltage at Load390.9 VLine Loss: 550.5 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A60.54 V (15.14%)339.5 V99.86 V (24.97%)3670.1 WDrop High
2.5 mm²24 A18 A36.32 V (9.08%)363.7 V59.92 V (14.98%)2202.1 WDrop High
4 mm²32 A25 A22.7 V (5.68%)377.3 V37.45 V (9.36%)1376.3 WDrop High
6 mm²41 A32 A15.14 V (3.78%)384.9 V24.97 V (6.24%)917.5 W~ ≤5%
10 mm²57 A44 A9.08 V (2.27%)390.9 V14.98 V (3.74%)550.5 W✓ OK (≤3%)
16 mm²76 A59 A5.68 V (1.42%)394.3 V9.36 V (2.34%)344.1 W✓ OK (≤3%)
25 mm²101 A78 A3.63 V (0.91%)396.4 V5.99 V (1.5%)220.2 W✓ OK (≤3%)
35 mm²125 A97 A2.59 V (0.65%)397.4 V4.28 V (1.07%)157.3 W✓ OK (≤3%)
50 mm²151 A118 A1.82 V (0.45%)398.2 V3.0 V (0.75%)110.1 W✓ OK (≤3%)
70 mm²192 A150 A1.3 V (0.32%)398.7 V2.14 V (0.53%)78.6 W✓ OK (≤3%)
95 mm²232 A181 A0.96 V (0.24%)399.0 V1.58 V (0.39%)57.9 W✓ OK (≤3%)
120 mm²269 A210 A0.76 V (0.19%)399.2 V1.25 V (0.31%)45.9 W✓ OK (≤3%)
150 mm²309 A241 A0.61 V (0.15%)399.4 V1.0 V (0.25%)36.7 W✓ OK (≤3%)
185 mm²353 A275 A0.49 V (0.12%)399.5 V0.81 V (0.2%)29.8 W✓ OK (≤3%)
240 mm²415 A324 A0.38 V (0.09%)399.6 V0.62 V (0.16%)22.9 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.08%)399.7 V0.5 V (0.12%)18.4 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.37 V (0.09%)13.8 W✓ OK (≤3%)

FAQ — Kabelarea för 35 Ampere vid 70 Meter (400V)

Vilken kabelarea krävs för 35A vid 70 meter (400V)?

För 35 Ampere över 70 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (9.08V / 2.27%).

Hur stor effekt motsvarar 35A vid 400V?

Det motsvarar 24.25 kW med en rekommenderad säkring på 35A.