⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 35 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 35 A över 30 m vid 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 6.49V (1.62%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 6.42V (1.6%)
Voltage at Load393.5 VLine Loss: 393.2 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A25.95 V (6.49%)374.1 V42.8 V (10.7%)1572.9 WDrop High
2.5 mm²24 A18 A15.57 V (3.89%)384.4 V25.68 V (6.42%)943.7 WDrop High
4 mm²32 A25 A9.73 V (2.43%)390.3 V16.05 V (4.01%)589.8 WDrop High
6 mm²41 A32 A6.49 V (1.62%)393.5 V10.7 V (2.67%)393.2 W✓ OK (≤3%)
10 mm²57 A44 A3.89 V (0.97%)396.1 V6.42 V (1.6%)235.9 W✓ OK (≤3%)
16 mm²76 A59 A2.43 V (0.61%)397.6 V4.01 V (1.0%)147.5 W✓ OK (≤3%)
25 mm²101 A78 A1.56 V (0.39%)398.4 V2.57 V (0.64%)94.4 W✓ OK (≤3%)
35 mm²125 A97 A1.11 V (0.28%)398.9 V1.83 V (0.46%)67.4 W✓ OK (≤3%)
50 mm²151 A118 A0.78 V (0.19%)399.2 V1.28 V (0.32%)47.2 W✓ OK (≤3%)
70 mm²192 A150 A0.56 V (0.14%)399.4 V0.92 V (0.23%)33.7 W✓ OK (≤3%)
95 mm²232 A181 A0.41 V (0.1%)399.6 V0.68 V (0.17%)24.8 W✓ OK (≤3%)
120 mm²269 A210 A0.32 V (0.08%)399.7 V0.53 V (0.13%)19.7 W✓ OK (≤3%)
150 mm²309 A241 A0.26 V (0.06%)399.7 V0.43 V (0.11%)15.7 W✓ OK (≤3%)
185 mm²353 A275 A0.21 V (0.05%)399.8 V0.35 V (0.09%)12.8 W✓ OK (≤3%)
240 mm²415 A324 A0.16 V (0.04%)399.8 V0.27 V (0.07%)9.8 W✓ OK (≤3%)
300 mm²477 A372 A0.13 V (0.03%)399.9 V0.21 V (0.05%)7.9 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.02%)399.9 V0.16 V (0.04%)5.9 W✓ OK (≤3%)

FAQ — Kabelarea för 35 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 35A vid 30 meter (400V)?

För 35 Ampere över 30 meter vid 400V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (6.49V / 1.62%).

Hur stor effekt motsvarar 35A vid 400V?

Det motsvarar 24.25 kW med en rekommenderad säkring på 35A.