Kabelarea för 375 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 35 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 2.34V (1.02%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.32V (1.01%)
Voltage at Load227.7 VLine Loss: 877.7 W
Max Power & Breaker86.25 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A374.5 V (162.83%)0.0 V617.75 V (268.59%)140437.5 WDrop High
2.5 mm²24 A18 A224.7 V (97.7%)5.3 V370.65 V (161.15%)84262.5 WDrop High
4 mm²32 A25 A140.44 V (61.06%)89.6 V231.66 V (100.72%)52664.1 WDrop High
6 mm²41 A32 A93.62 V (40.71%)136.4 V154.44 V (67.15%)35109.4 WDrop High
10 mm²57 A44 A56.17 V (24.42%)173.8 V92.66 V (40.29%)21065.6 WDrop High
16 mm²76 A59 A35.11 V (15.26%)194.9 V57.91 V (25.18%)13166.0 WDrop High
25 mm²101 A78 A22.47 V (9.77%)207.5 V37.06 V (16.12%)8426.2 WDrop High
35 mm²125 A97 A16.05 V (6.98%)213.9 V26.47 V (11.51%)6018.8 WDrop High
50 mm²151 A118 A11.23 V (4.88%)218.8 V18.53 V (8.06%)4213.1 WDrop High
70 mm²192 A150 A8.03 V (3.49%)222.0 V13.24 V (5.76%)3009.4 WDrop High
95 mm²232 A181 A5.91 V (2.57%)224.1 V9.75 V (4.24%)2217.4 WDrop High
120 mm²269 A210 A4.68 V (2.04%)225.3 V7.72 V (3.36%)1755.5 WDrop High
150 mm²309 A241 A3.74 V (1.63%)226.3 V6.18 V (2.69%)1404.4 WDrop High
185 mm²353 A275 A3.04 V (1.32%)227.0 V5.01 V (2.18%)1138.7 WDrop High
240 mm²415 A324 A2.34 V (1.02%)227.7 V3.86 V (1.68%)877.7 W✓ OK (≤3%)
300 mm²477 A372 A1.87 V (0.81%)228.1 V3.09 V (1.34%)702.2 W✓ OK (≤3%)
400 mm²570 A445 A1.4 V (0.61%)228.6 V2.32 V (1.01%)526.6 W✓ OK (≤3%)

FAQ — Kabelarea för 375 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 375A vid 35 meter (230V)?

För 375 Ampere över 35 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (2.34V / 1.02%).

Hur stor effekt motsvarar 375A vid 230V?

Det motsvarar 86.25 kW med en rekommenderad säkring på 400A.