Kabelarea för 375 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 35 m vid 230V.
Copper Cable (≤3% Drop)240 mm²Drop: 2.34V (1.02%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.32V (1.01%)
Voltage at Load227.7 VLine Loss: 877.7 W
Max Power & Breaker86.25 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 374.5 V (162.83%) | 0.0 V | 617.75 V (268.59%) | 140437.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 224.7 V (97.7%) | 5.3 V | 370.65 V (161.15%) | 84262.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 140.44 V (61.06%) | 89.6 V | 231.66 V (100.72%) | 52664.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 93.62 V (40.71%) | 136.4 V | 154.44 V (67.15%) | 35109.4 W | Drop High |
| 10 mm² | 57 A | 44 A | 56.17 V (24.42%) | 173.8 V | 92.66 V (40.29%) | 21065.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 35.11 V (15.26%) | 194.9 V | 57.91 V (25.18%) | 13166.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 22.47 V (9.77%) | 207.5 V | 37.06 V (16.12%) | 8426.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 16.05 V (6.98%) | 213.9 V | 26.47 V (11.51%) | 6018.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 11.23 V (4.88%) | 218.8 V | 18.53 V (8.06%) | 4213.1 W | Drop High |
| 70 mm² | 192 A | 150 A | 8.03 V (3.49%) | 222.0 V | 13.24 V (5.76%) | 3009.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 5.91 V (2.57%) | 224.1 V | 9.75 V (4.24%) | 2217.4 W | Drop High |
| 120 mm² | 269 A | 210 A | 4.68 V (2.04%) | 225.3 V | 7.72 V (3.36%) | 1755.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 3.74 V (1.63%) | 226.3 V | 6.18 V (2.69%) | 1404.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.04 V (1.32%) | 227.0 V | 5.01 V (2.18%) | 1138.7 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.34 V (1.02%) | 227.7 V | 3.86 V (1.68%) | 877.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.87 V (0.81%) | 228.1 V | 3.09 V (1.34%) | 702.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.4 V (0.61%) | 228.6 V | 2.32 V (1.01%) | 526.6 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 375 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 375A vid 35 meter (230V)?
För 375 Ampere över 35 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (2.34V / 1.02%).
Hur stor effekt motsvarar 375A vid 230V?
Det motsvarar 86.25 kW med en rekommenderad säkring på 400A.
Related Lengths & Currents (230V)
375A · 5m (230V)375A · 10m (230V)375A · 15m (230V)375A · 20m (230V)375A · 25m (230V)375A · 30m (230V)375A · 40m (230V)375A · 45m (230V)375A · 50m (230V)375A · 60m (230V)375A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)