Kabelarea för 100 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 35 m vid 230V.
Copper Cable (≤3% Drop)25 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.94V (2.15%)
Voltage at Load224.0 VLine Loss: 599.2 W
Max Power & Breaker23.0 kW100A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 99.87 V (43.42%) | 130.1 V | 164.73 V (71.62%) | 9986.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 59.92 V (26.05%) | 170.1 V | 98.84 V (42.97%) | 5992.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 37.45 V (16.28%) | 192.6 V | 61.78 V (26.86%) | 3745.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 24.97 V (10.86%) | 205.0 V | 41.18 V (17.91%) | 2496.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 14.98 V (6.51%) | 215.0 V | 24.71 V (10.74%) | 1498.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 9.36 V (4.07%) | 220.6 V | 15.44 V (6.71%) | 936.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 5.99 V (2.61%) | 224.0 V | 9.88 V (4.3%) | 599.2 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 4.28 V (1.86%) | 225.7 V | 7.06 V (3.07%) | 428.0 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 3.0 V (1.3%) | 227.0 V | 4.94 V (2.15%) | 299.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 214.0 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.58 V (0.69%) | 228.4 V | 2.6 V (1.13%) | 157.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.25 V (0.54%) | 228.8 V | 2.06 V (0.9%) | 124.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 1.0 V (0.43%) | 229.0 V | 1.65 V (0.72%) | 99.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.81 V (0.35%) | 229.2 V | 1.34 V (0.58%) | 81.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.62 V (0.27%) | 229.4 V | 1.03 V (0.45%) | 62.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.5 V (0.22%) | 229.5 V | 0.82 V (0.36%) | 49.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.37 V (0.16%) | 229.6 V | 0.62 V (0.27%) | 37.5 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 100 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 100A vid 35 meter (230V)?
För 100 Ampere över 35 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).
Hur stor effekt motsvarar 100A vid 230V?
Det motsvarar 23.0 kW med en rekommenderad säkring på 100A.
Related Lengths & Currents (230V)
100A · 5m (230V)100A · 10m (230V)100A · 15m (230V)100A · 20m (230V)100A · 25m (230V)100A · 30m (230V)100A · 40m (230V)100A · 45m (230V)100A · 50m (230V)100A · 60m (230V)100A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)