Kabelarea för 100 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 35 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 4.94V (2.15%)
Voltage at Load224.0 VLine Loss: 599.2 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A99.87 V (43.42%)130.1 V164.73 V (71.62%)9986.7 WDrop High
2.5 mm²24 A18 A59.92 V (26.05%)170.1 V98.84 V (42.97%)5992.0 WDrop High
4 mm²32 A25 A37.45 V (16.28%)192.6 V61.78 V (26.86%)3745.0 WDrop High
6 mm²41 A32 A24.97 V (10.86%)205.0 V41.18 V (17.91%)2496.7 WDrop High
10 mm²57 A44 A14.98 V (6.51%)215.0 V24.71 V (10.74%)1498.0 WDrop High
16 mm²76 A59 A9.36 V (4.07%)220.6 V15.44 V (6.71%)936.2 WDrop High
25 mm²101 A78 A5.99 V (2.61%)224.0 V9.88 V (4.3%)599.2 W✓ OK (≤3%)
35 mm²125 A97 A4.28 V (1.86%)225.7 V7.06 V (3.07%)428.0 W✓ OK (≤3%)
50 mm²151 A118 A3.0 V (1.3%)227.0 V4.94 V (2.15%)299.6 W✓ OK (≤3%)
70 mm²192 A150 A2.14 V (0.93%)227.9 V3.53 V (1.53%)214.0 W✓ OK (≤3%)
95 mm²232 A181 A1.58 V (0.69%)228.4 V2.6 V (1.13%)157.7 W✓ OK (≤3%)
120 mm²269 A210 A1.25 V (0.54%)228.8 V2.06 V (0.9%)124.8 W✓ OK (≤3%)
150 mm²309 A241 A1.0 V (0.43%)229.0 V1.65 V (0.72%)99.9 W✓ OK (≤3%)
185 mm²353 A275 A0.81 V (0.35%)229.2 V1.34 V (0.58%)81.0 W✓ OK (≤3%)
240 mm²415 A324 A0.62 V (0.27%)229.4 V1.03 V (0.45%)62.4 W✓ OK (≤3%)
300 mm²477 A372 A0.5 V (0.22%)229.5 V0.82 V (0.36%)49.9 W✓ OK (≤3%)
400 mm²570 A445 A0.37 V (0.16%)229.6 V0.62 V (0.27%)37.5 W✓ OK (≤3%)

FAQ — Kabelarea för 100 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 100A vid 35 meter (230V)?

För 100 Ampere över 35 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).

Hur stor effekt motsvarar 100A vid 230V?

Det motsvarar 23.0 kW med en rekommenderad säkring på 100A.