Kabelarea för 40 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 40 A över 35 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 5.99V (2.61%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 6.18V (2.69%)
Voltage at Load224.0 VLine Loss: 239.7 W
Max Power & Breaker9.2 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A39.95 V (17.37%)190.1 V65.89 V (28.65%)1597.9 WDrop High
2.5 mm²24 A18 A23.97 V (10.42%)206.0 V39.54 V (17.19%)958.7 WDrop High
4 mm²32 A25 A14.98 V (6.51%)215.0 V24.71 V (10.74%)599.2 WDrop High
6 mm²41 A32 A9.99 V (4.34%)220.0 V16.47 V (7.16%)399.5 W~ ≤5%
10 mm²57 A44 A5.99 V (2.61%)224.0 V9.88 V (4.3%)239.7 W✓ OK (≤3%)
16 mm²76 A59 A3.75 V (1.63%)226.3 V6.18 V (2.69%)149.8 W✓ OK (≤3%)
25 mm²101 A78 A2.4 V (1.04%)227.6 V3.95 V (1.72%)95.9 W✓ OK (≤3%)
35 mm²125 A97 A1.71 V (0.74%)228.3 V2.82 V (1.23%)68.5 W✓ OK (≤3%)
50 mm²151 A118 A1.2 V (0.52%)228.8 V1.98 V (0.86%)47.9 W✓ OK (≤3%)
70 mm²192 A150 A0.86 V (0.37%)229.1 V1.41 V (0.61%)34.2 W✓ OK (≤3%)
95 mm²232 A181 A0.63 V (0.27%)229.4 V1.04 V (0.45%)25.2 W✓ OK (≤3%)
120 mm²269 A210 A0.5 V (0.22%)229.5 V0.82 V (0.36%)20.0 W✓ OK (≤3%)
150 mm²309 A241 A0.4 V (0.17%)229.6 V0.66 V (0.29%)16.0 W✓ OK (≤3%)
185 mm²353 A275 A0.32 V (0.14%)229.7 V0.53 V (0.23%)13.0 W✓ OK (≤3%)
240 mm²415 A324 A0.25 V (0.11%)229.8 V0.41 V (0.18%)10.0 W✓ OK (≤3%)
300 mm²477 A372 A0.2 V (0.09%)229.8 V0.33 V (0.14%)8.0 W✓ OK (≤3%)
400 mm²570 A445 A0.15 V (0.07%)229.9 V0.25 V (0.11%)6.0 W✓ OK (≤3%)

FAQ — Kabelarea för 40 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 40A vid 35 meter (230V)?

För 40 Ampere över 35 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (5.99V / 2.61%).

Hur stor effekt motsvarar 40A vid 230V?

Det motsvarar 9.2 kW med en rekommenderad säkring på 40A.