⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 400 Ampere vid 80 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 400 A över 80 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 2282.7 W
Max Power & Breaker92.0 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A913.07 V (396.99%)0.0 V1506.13 V (654.84%)365226.7 WDrop High
2.5 mm²24 A18 A547.84 V (238.19%)0.0 V903.68 V (392.9%)219136.0 WDrop High
4 mm²32 A25 A342.4 V (148.87%)0.0 V564.8 V (245.57%)136960.0 WDrop High
6 mm²41 A32 A228.27 V (99.25%)1.7 V376.53 V (163.71%)91306.7 WDrop High
10 mm²57 A44 A136.96 V (59.55%)93.0 V225.92 V (98.23%)54784.0 WDrop High
16 mm²76 A59 A85.6 V (37.22%)144.4 V141.2 V (61.39%)34240.0 WDrop High
25 mm²101 A78 A54.78 V (23.82%)175.2 V90.37 V (39.29%)21913.6 WDrop High
35 mm²125 A97 A39.13 V (17.01%)190.9 V64.55 V (28.06%)15652.6 WDrop High
50 mm²151 A118 A27.39 V (11.91%)202.6 V45.18 V (19.65%)10956.8 WDrop High
70 mm²192 A150 A19.57 V (8.51%)210.4 V32.27 V (14.03%)7826.3 WDrop High
95 mm²232 A181 A14.42 V (6.27%)215.6 V23.78 V (10.34%)5766.7 WDrop High
120 mm²269 A210 A11.41 V (4.96%)218.6 V18.83 V (8.19%)4565.3 WDrop High
150 mm²309 A241 A9.13 V (3.97%)220.9 V15.06 V (6.55%)3652.3 WDrop High
185 mm²353 A275 A7.4 V (3.22%)222.6 V12.21 V (5.31%)2961.3 WDrop High
240 mm²415 A324 A5.71 V (2.48%)224.3 V9.41 V (4.09%)2282.7 W✓ OK (≤3%)
300 mm²477 A372 A4.57 V (1.98%)225.4 V7.53 V (3.27%)1826.1 W✓ OK (≤3%)
400 mm²570 A445 A3.42 V (1.49%)226.6 V5.65 V (2.46%)1369.6 W✓ OK (≤3%)

FAQ — Kabelarea för 400 Ampere vid 80 Meter (230V)

Vilken kabelarea krävs för 400A vid 80 meter (230V)?

För 400 Ampere över 80 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (5.71V / 2.48%).

Hur stor effekt motsvarar 400A vid 230V?

Det motsvarar 92.0 kW med en rekommenderad säkring på 400A.