Kabelarea för 16 Ampere vid 30 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 30 m vid 230V.

Copper Cable (≤3% Drop)4 mm²Drop: 5.14V (2.23%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 5.65V (2.46%)
Voltage at Load224.9 VLine Loss: 82.2 W
Max Power & Breaker3.68 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A13.7 V (5.95%)216.3 V22.59 V (9.82%)219.1 WDrop High
2.5 mm²24 A18 A8.22 V (3.57%)221.8 V13.56 V (5.89%)131.5 W~ ≤5%
4 mm²32 A25 A5.14 V (2.23%)224.9 V8.47 V (3.68%)82.2 W✓ OK (≤3%)
6 mm²41 A32 A3.42 V (1.49%)226.6 V5.65 V (2.46%)54.8 W✓ OK (≤3%)
10 mm²57 A44 A2.05 V (0.89%)227.9 V3.39 V (1.47%)32.9 W✓ OK (≤3%)
16 mm²76 A59 A1.28 V (0.56%)228.7 V2.12 V (0.92%)20.5 W✓ OK (≤3%)
25 mm²101 A78 A0.82 V (0.36%)229.2 V1.36 V (0.59%)13.1 W✓ OK (≤3%)
35 mm²125 A97 A0.59 V (0.26%)229.4 V0.97 V (0.42%)9.4 W✓ OK (≤3%)
50 mm²151 A118 A0.41 V (0.18%)229.6 V0.68 V (0.29%)6.6 W✓ OK (≤3%)
70 mm²192 A150 A0.29 V (0.13%)229.7 V0.48 V (0.21%)4.7 W✓ OK (≤3%)
95 mm²232 A181 A0.22 V (0.09%)229.8 V0.36 V (0.16%)3.5 W✓ OK (≤3%)
120 mm²269 A210 A0.17 V (0.07%)229.8 V0.28 V (0.12%)2.7 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.06%)229.9 V0.23 V (0.1%)2.2 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.05%)229.9 V0.18 V (0.08%)1.8 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.14 V (0.06%)1.4 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.11 V (0.05%)1.1 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)229.9 V0.08 V (0.04%)0.8 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 30 Meter (230V)

Vilken kabelarea krävs för 16A vid 30 meter (230V)?

För 16 Ampere över 30 meter vid 230V rekommenderas 4 mm² kopparkabel för att hålla spänningsfallet under 3% (5.14V / 2.23%).

Hur stor effekt motsvarar 16A vid 230V?

Det motsvarar 3.68 kW med en rekommenderad säkring på 16A.