Kabelarea för 475 Ampere vid 100 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 100 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 5.87V (1.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.26V (1.82%)
Voltage at Load394.1 VLine Loss: 4828.4 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1173.75 V (293.44%)0.0 V1936.14 V (484.04%)965675.0 WDrop High
2.5 mm²24 A18 A704.25 V (176.06%)0.0 V1161.69 V (290.42%)579405.0 WDrop High
4 mm²32 A25 A440.16 V (110.04%)0.0 V726.05 V (181.51%)362128.1 WDrop High
6 mm²41 A32 A293.44 V (73.36%)106.6 V484.04 V (121.01%)241418.7 WDrop High
10 mm²57 A44 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
16 mm²76 A59 A110.04 V (27.51%)290.0 V181.51 V (45.38%)90532.0 WDrop High
25 mm²101 A78 A70.43 V (17.61%)329.6 V116.17 V (29.04%)57940.5 WDrop High
35 mm²125 A97 A50.3 V (12.58%)349.7 V82.98 V (20.74%)41386.1 WDrop High
50 mm²151 A118 A35.21 V (8.8%)364.8 V58.08 V (14.52%)28970.2 WDrop High
70 mm²192 A150 A25.15 V (6.29%)374.8 V41.49 V (10.37%)20693.0 WDrop High
95 mm²232 A181 A18.53 V (4.63%)381.5 V30.57 V (7.64%)15247.5 WDrop High
120 mm²269 A210 A14.67 V (3.67%)385.3 V24.2 V (6.05%)12070.9 WDrop High
150 mm²309 A241 A11.74 V (2.93%)388.3 V19.36 V (4.84%)9656.8 WDrop High
185 mm²353 A275 A9.52 V (2.38%)390.5 V15.7 V (3.92%)7829.8 WDrop High
240 mm²415 A324 A7.34 V (1.83%)392.7 V12.1 V (3.03%)6035.5 WDrop High
300 mm²477 A372 A5.87 V (1.47%)394.1 V9.68 V (2.42%)4828.4 W✓ OK (≤3%)
400 mm²570 A445 A4.4 V (1.1%)395.6 V7.26 V (1.82%)3621.3 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 100 Meter (400V)

Vilken kabelarea krävs för 475A vid 100 meter (400V)?

För 475 Ampere över 100 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.87V / 1.47%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.