Kabelarea för 475 Ampere vid 100 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 100 m vid 400V.
Copper Cable (≤3% Drop)300 mm²Drop: 5.87V (1.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.26V (1.82%)
Voltage at Load394.1 VLine Loss: 4828.4 W
Max Power & Breaker329.09 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1173.75 V (293.44%) | 0.0 V | 1936.14 V (484.04%) | 965675.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 704.25 V (176.06%) | 0.0 V | 1161.69 V (290.42%) | 579405.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 440.16 V (110.04%) | 0.0 V | 726.05 V (181.51%) | 362128.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 293.44 V (73.36%) | 106.6 V | 484.04 V (121.01%) | 241418.7 W | Drop High |
| 10 mm² | 57 A | 44 A | 176.06 V (44.02%) | 223.9 V | 290.42 V (72.61%) | 144851.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 110.04 V (27.51%) | 290.0 V | 181.51 V (45.38%) | 90532.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 70.43 V (17.61%) | 329.6 V | 116.17 V (29.04%) | 57940.5 W | Drop High |
| 35 mm² | 125 A | 97 A | 50.3 V (12.58%) | 349.7 V | 82.98 V (20.74%) | 41386.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 35.21 V (8.8%) | 364.8 V | 58.08 V (14.52%) | 28970.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 25.15 V (6.29%) | 374.8 V | 41.49 V (10.37%) | 20693.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 18.53 V (4.63%) | 381.5 V | 30.57 V (7.64%) | 15247.5 W | Drop High |
| 120 mm² | 269 A | 210 A | 14.67 V (3.67%) | 385.3 V | 24.2 V (6.05%) | 12070.9 W | Drop High |
| 150 mm² | 309 A | 241 A | 11.74 V (2.93%) | 388.3 V | 19.36 V (4.84%) | 9656.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 9.52 V (2.38%) | 390.5 V | 15.7 V (3.92%) | 7829.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 7.34 V (1.83%) | 392.7 V | 12.1 V (3.03%) | 6035.5 W | Drop High |
| 300 mm² | 477 A | 372 A | 5.87 V (1.47%) | 394.1 V | 9.68 V (2.42%) | 4828.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 4.4 V (1.1%) | 395.6 V | 7.26 V (1.82%) | 3621.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 475 Ampere vid 100 Meter (400V)
Vilken kabelarea krävs för 475A vid 100 meter (400V)?
För 475 Ampere över 100 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (5.87V / 1.47%).
Hur stor effekt motsvarar 475A vid 400V?
Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.
Related Lengths & Currents (400V)
475A · 5m (400V)475A · 10m (400V)475A · 15m (400V)475A · 20m (400V)475A · 25m (400V)475A · 30m (400V)475A · 35m (400V)475A · 40m (400V)475A · 45m (400V)475A · 50m (400V)475A · 60m (400V)475A · 70m (400V)10A · 100m (400V)16A · 100m (400V)20A · 100m (400V)25A · 100m (400V)32A · 100m (400V)40A · 100m (400V)50A · 100m (400V)63A · 100m (400V)80A · 100m (400V)100A · 100m (400V)125A · 100m (400V)160A · 100m (400V)200A · 100m (400V)