Kabelarea för 475 Ampere vid 30 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 30 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 1.76V (0.44%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.18V (0.54%)
Voltage at Load398.2 VLine Loss: 1448.5 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 30m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A352.13 V (88.03%)47.9 V580.84 V (145.21%)289702.5 WDrop High
2.5 mm²24 A18 A211.28 V (52.82%)188.7 V348.51 V (87.13%)173821.5 WDrop High
4 mm²32 A25 A132.05 V (33.01%)268.0 V217.82 V (54.45%)108638.4 WDrop High
6 mm²41 A32 A88.03 V (22.01%)312.0 V145.21 V (36.3%)72425.6 WDrop High
10 mm²57 A44 A52.82 V (13.2%)347.2 V87.13 V (21.78%)43455.4 WDrop High
16 mm²76 A59 A33.01 V (8.25%)367.0 V54.45 V (13.61%)27159.6 WDrop High
25 mm²101 A78 A21.13 V (5.28%)378.9 V34.85 V (8.71%)17382.2 WDrop High
35 mm²125 A97 A15.09 V (3.77%)384.9 V24.89 V (6.22%)12415.8 WDrop High
50 mm²151 A118 A10.56 V (2.64%)389.4 V17.43 V (4.36%)8691.1 WDrop High
70 mm²192 A150 A7.55 V (1.89%)392.5 V12.45 V (3.11%)6207.9 WDrop High
95 mm²232 A181 A5.56 V (1.39%)394.4 V9.17 V (2.29%)4574.2 WDrop High
120 mm²269 A210 A4.4 V (1.1%)395.6 V7.26 V (1.82%)3621.3 WDrop High
150 mm²309 A241 A3.52 V (0.88%)396.5 V5.81 V (1.45%)2897.0 WDrop High
185 mm²353 A275 A2.86 V (0.71%)397.1 V4.71 V (1.18%)2348.9 WDrop High
240 mm²415 A324 A2.2 V (0.55%)397.8 V3.63 V (0.91%)1810.6 WDrop High
300 mm²477 A372 A1.76 V (0.44%)398.2 V2.9 V (0.73%)1448.5 W✓ OK (≤3%)
400 mm²570 A445 A1.32 V (0.33%)398.7 V2.18 V (0.54%)1086.4 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 30 Meter (400V)

Vilken kabelarea krävs för 475A vid 30 meter (400V)?

För 475 Ampere över 30 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (1.76V / 0.44%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.