Kabelarea för 475 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 475 A över 60 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 3.52V (0.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.36V (1.09%)
Voltage at Load396.5 VLine Loss: 2897.0 W
Max Power & Breaker329.09 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A704.25 V (176.06%)0.0 V1161.69 V (290.42%)579405.0 WDrop High
2.5 mm²24 A18 A422.55 V (105.64%)0.0 V697.01 V (174.25%)347643.0 WDrop High
4 mm²32 A25 A264.09 V (66.02%)135.9 V435.63 V (108.91%)217276.9 WDrop High
6 mm²41 A32 A176.06 V (44.02%)223.9 V290.42 V (72.61%)144851.2 WDrop High
10 mm²57 A44 A105.64 V (26.41%)294.4 V174.25 V (43.56%)86910.8 WDrop High
16 mm²76 A59 A66.02 V (16.51%)334.0 V108.91 V (27.23%)54319.2 WDrop High
25 mm²101 A78 A42.26 V (10.56%)357.7 V69.7 V (17.43%)34764.3 WDrop High
35 mm²125 A97 A30.18 V (7.55%)369.8 V49.79 V (12.45%)24831.6 WDrop High
50 mm²151 A118 A21.13 V (5.28%)378.9 V34.85 V (8.71%)17382.2 WDrop High
70 mm²192 A150 A15.09 V (3.77%)384.9 V24.89 V (6.22%)12415.8 WDrop High
95 mm²232 A181 A11.12 V (2.78%)388.9 V18.34 V (4.59%)9148.5 WDrop High
120 mm²269 A210 A8.8 V (2.2%)391.2 V14.52 V (3.63%)7242.6 WDrop High
150 mm²309 A241 A7.04 V (1.76%)393.0 V11.62 V (2.9%)5794.1 WDrop High
185 mm²353 A275 A5.71 V (1.43%)394.3 V9.42 V (2.35%)4697.9 WDrop High
240 mm²415 A324 A4.4 V (1.1%)395.6 V7.26 V (1.82%)3621.3 WDrop High
300 mm²477 A372 A3.52 V (0.88%)396.5 V5.81 V (1.45%)2897.0 W✓ OK (≤3%)
400 mm²570 A445 A2.64 V (0.66%)397.4 V4.36 V (1.09%)2172.8 W✓ OK (≤3%)

FAQ — Kabelarea för 475 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 475A vid 60 meter (400V)?

För 475 Ampere över 60 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (3.52V / 0.88%).

Hur stor effekt motsvarar 475A vid 400V?

Det motsvarar 329.09 kW med en rekommenderad säkring på 500A.