Kabelarea för 5 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 35 m vid 230V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 4.99V (2.17%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 4.94V (2.15%)
Voltage at Load225.0 VLine Loss: 25.0 W
Max Power & Breaker1.15 kW6A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4.99 V (2.17%) | 225.0 V | 8.24 V (3.58%) | 25.0 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 3.0 V (1.3%) | 227.0 V | 4.94 V (2.15%) | 15.0 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 1.87 V (0.81%) | 228.1 V | 3.09 V (1.34%) | 9.4 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 1.25 V (0.54%) | 228.8 V | 2.06 V (0.9%) | 6.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.75 V (0.33%) | 229.3 V | 1.24 V (0.54%) | 3.7 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.47 V (0.2%) | 229.5 V | 0.77 V (0.34%) | 2.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.3 V (0.13%) | 229.7 V | 0.49 V (0.21%) | 1.5 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.21 V (0.09%) | 229.8 V | 0.35 V (0.15%) | 1.1 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.15 V (0.07%) | 229.9 V | 0.25 V (0.11%) | 0.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.11 V (0.05%) | 229.9 V | 0.18 V (0.08%) | 0.5 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.08 V (0.03%) | 229.9 V | 0.13 V (0.06%) | 0.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.06 V (0.03%) | 229.9 V | 0.1 V (0.04%) | 0.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.05 V (0.02%) | 230.0 V | 0.08 V (0.04%) | 0.2 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 0.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.03 V (0.01%) | 230.0 V | 0.05 V (0.02%) | 0.2 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.02 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.02 V (0.01%) | 230.0 V | 0.03 V (0.01%) | 0.1 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 5 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 5A vid 35 meter (230V)?
För 5 Ampere över 35 meter vid 230V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (4.99V / 2.17%).
Hur stor effekt motsvarar 5A vid 230V?
Det motsvarar 1.15 kW med en rekommenderad säkring på 6A.
Related Lengths & Currents (230V)
5A · 5m (230V)5A · 10m (230V)5A · 15m (230V)5A · 20m (230V)5A · 25m (230V)5A · 30m (230V)5A · 40m (230V)5A · 45m (230V)5A · 50m (230V)5A · 60m (230V)5A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)