Kabelarea för 50 Ampere vid 10 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 50 A över 10 m vid 230V.

Copper Cable (≤3% Drop)10 mm²Drop: 2.14V (0.93%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 2.21V (0.96%)
Voltage at Load227.9 VLine Loss: 107.0 W
Max Power & Breaker11.5 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.27 V (6.2%)215.7 V23.53 V (10.23%)713.3 WDrop High
2.5 mm²24 A18 A8.56 V (3.72%)221.4 V14.12 V (6.14%)428.0 WDrop High
4 mm²32 A25 A5.35 V (2.33%)224.7 V8.82 V (3.84%)267.5 WDrop High
6 mm²41 A32 A3.57 V (1.55%)226.4 V5.88 V (2.56%)178.3 WDrop High
10 mm²57 A44 A2.14 V (0.93%)227.9 V3.53 V (1.53%)107.0 W✓ OK (≤3%)
16 mm²76 A59 A1.34 V (0.58%)228.7 V2.21 V (0.96%)66.9 W✓ OK (≤3%)
25 mm²101 A78 A0.86 V (0.37%)229.1 V1.41 V (0.61%)42.8 W✓ OK (≤3%)
35 mm²125 A97 A0.61 V (0.27%)229.4 V1.01 V (0.44%)30.6 W✓ OK (≤3%)
50 mm²151 A118 A0.43 V (0.19%)229.6 V0.71 V (0.31%)21.4 W✓ OK (≤3%)
70 mm²192 A150 A0.31 V (0.13%)229.7 V0.5 V (0.22%)15.3 W✓ OK (≤3%)
95 mm²232 A181 A0.23 V (0.1%)229.8 V0.37 V (0.16%)11.3 W✓ OK (≤3%)
120 mm²269 A210 A0.18 V (0.08%)229.8 V0.29 V (0.13%)8.9 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.06%)229.9 V0.24 V (0.1%)7.1 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.05%)229.9 V0.19 V (0.08%)5.8 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.15 V (0.06%)4.5 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.12 V (0.05%)3.6 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)229.9 V0.09 V (0.04%)2.7 W✓ OK (≤3%)

FAQ — Kabelarea för 50 Ampere vid 10 Meter (230V)

Vilken kabelarea krävs för 50A vid 10 meter (230V)?

För 50 Ampere över 10 meter vid 230V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (2.14V / 0.93%).

Hur stor effekt motsvarar 50A vid 230V?

Det motsvarar 11.5 kW med en rekommenderad säkring på 50A.